12
|
Commissioning
Installer reference guide
199
08CA + EHY EHYHBH/X08A + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1G – 2022.09
4
Go to [A.7.3.4]
>
Installer settings
>
Commissioning
>
Air
purge
>
Start air purge
and press to start the air purge function.
Result:
The manual air purge starts and the following screen appears.
01:18
Tue
Air purge
l/min
Low
SHC
Yes
0.5
Flow rate
Speed
Circuit
Bypass
Stop
Adjust
Scroll
5
Use the and buttons to scroll to
Speed
.
6
Use the and buttons to set the desired pump speed.
Result:
Low
Result:
High
7
If applicable, set the desired position of the 3-way valve (space heating/
domestic hot water). Use the and buttons to scroll to
Circuit
.
8
Use the and buttons to set the desired position of the 3-way valve.
Result:
SHC
or
Tank
9
Set the desired position of the bypass valve. Use the and buttons to scroll to
Bypass
.
10
Use the and buttons to set the desired position of the bypass valve.
Result:
No
(boiler not bypassed)
Result:
Yes
(boiler bypassed)
To perform an automatic air purge
Prerequisite:
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1
Set the user permission level to Installer. See
"To set the user permission level
2
Set the air purge mode: go to [A.7.3.1]
>
Installer settings
>
Commissioning
>
Air purge
>
Type
.
3
Select
Automatic
and press .
4
Go to [A.7.3.4]
>
Installer settings
>
Commissioning
>
Air
purge
>
Start air purge
and press to start the air purge function.
Result:
Air purging will start and the following screen will be shown.
01:18
Tue
Air purge
l/min
Low
SHC
Yes
0.5
Flow rate
Speed
Circuit
Bypass
Stop
Adjust
Scroll
To interrupt air purge
1
Press and press to confirm the interruption of the air purge function.
12.4.3 To perform a test run
Prerequisite:
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
Содержание Altherma EHYHBH05A Series
Страница 261: ......
Страница 262: ......
Страница 263: ......
Страница 264: ...4P355634 1G 2022 09 Copyright 2013 Daikin Verantwortung f r Energie und Umwelt...