7
|
Unit installation
Installer reference guide
84
EPRA14~18D + ETSH/X(B)16P30+50E
Daikin Altherma 3 H HT ECH₂O
4P679467-1B – 2022.09
7.3.8 To prevent the outdoor unit from falling over
In case the unit is installed in places where strong wind can tilt the unit, take
following measure:
1
Prepare 2 cables as indicated in the following illustration (field supply).
2
Place the 2 cables over the outdoor unit.
3
Insert a rubber sheet between the cables and the outdoor unit to prevent the
cables from scratching the paint (field supply).
4
Attach the ends of the cables.
5
Tighten the cables.
NOTICE
Discharge grille.
Do NOT use too much force to prevent damage to the discharge
grille.
7.4 Mounting the indoor unit
7.4.1 About mounting the indoor unit
When
You have to mount the outdoor and indoor unit before you can connect the water
piping.
Typical workflow
Mounting the indoor unit typically consists of the following stages:
1
Installing the indoor unit.
7.4.2 Precautions when mounting the indoor unit
INFORMATION
Also read the precautions and requirements in the following chapters:
▪
"2 General safety precautions"
▪