Application guidelines
Installer reference guide
50
EPRA14~18D + ETSH/X(B)16P30+50E
Daikin Altherma 3 H HT ECH₂O
4P679467-1B – 2022.09
▪
Install non-return valves.
▪
The external heat source is controlled by the ON/OFF signal on the indoor unit
(X12M/3 and X12M/4). See
"9.3.10 To connect the changeover to external heat
131].
▪
To setup the heat emitters, see
"6.2 Setting up the space heating/cooling
34].
Configuration
Via the user interface (configuration wizard):
▪
Set the use of a direct (SH) bivalent system as external heat source.
▪
Set the bivalent temperature and hysteresis.
NOTICE
▪
Make sure the bivalent hysteresis has enough differential to prevent frequent
changeover between indoor unit and auxiliary boiler.
▪
Because the outdoor temperature is measured by the outdoor unit air
thermistor, install the outdoor unit in the shadow so that it is NOT influenced or
turned ON/OFF by direct sunlight.
▪
Frequent changeover may cause corrosion of the auxiliary boiler. Contact the
manufacturer of the auxiliary boiler for more information.
Changeover to external heat source decided by an auxiliary contact
▪
Only possible in external room thermostat control AND one leaving water
temperature zone (see
"6.2 Setting up the space heating/cooling system"
34]).
▪
The auxiliary contact can be:
-
An outdoor temperature thermostat
-
An electricity tariff contact
-
A manually operated contact
-
…
▪
Setup: Connect the following field wiring:
L
N
H
Com
A
K2A
K1A
X12M
BTI
K2A
K1A
Indoor/Auto/Boiler
15 22
X Y
Indoor
B
TI
Boiler thermostat input
A
Auxiliary contact (normally closed)
H
Heating demand room thermostat (optional)
K1A
Auxiliary relay for activation of indoor unit (field supply)
K2A
Auxiliary relay for activation of boiler (field supply)
Indoor
Indoor unit
Auto
Automatic
Boiler
Boiler