15
|
Disposal
Installer reference guide
268
EPRA14~18D + ETSH/X(B)16P30+50E
Daikin Altherma 3 H HT ECH₂O
4P679467-1B – 2022.09
To deactivate the recovery mode
After recovering refrigerant, deactivate the recovery mode as follows:
#
Procedure
7-LEDs display
(a)
H1P H2P H3P H4P H5P H6P H7P
1
Press and hold
BS1
for 5 seconds.
2
Press
BS2
9 times.
3
Press
BS3
once.
4
Press
BS2
once.
5
Press
BS3
once.
6
Press
BS3
once.
7
Press
BS1
once to return to the
default situation.
(a)
= OFF, = ON, and = flashing.
Result:
The recovery mode is deactivated. The unit returns the electronic
expansion valves / solenoid valves to their initial state.
INFORMATION
Power OFF
. When power is turned OFF and turned ON again, the recovery mode is
deactivated automatically.