Depending on the demand, the indoor unit supplies different leaving water
temperature matching the design temperature of the different heat emitters.
-
Underfloor heating has the best performance with the heat pump system.
6.3 Setting up the domestic hot water tank
6.3.1 System layout – Integrated DHW tank
M
M
b
c
a
d
g
e
h
i
i
i
j
j
f
k
i
HPC1
UI
FHL1
FHL2 FHL3
HPC2
HPC3
a
c
i
a
Outdoor unit
b
Indoor unit
c
Heat exchanger
d
Backup heater
e
Motorised 3‑way valve (switch between space heating and domestic hot water)
f
Motorised 3‑way valve (mixing the main zone)
g
Main pump
h
Additional pump
i
Shut-off valve
j
Collector (field supply)
k
Domestic hot water tank
FHL1...3
Floor heating loops (field supply)
UI
User interface (field supply)
HPC1...3
Heat pump convectors (field supply)
6.3.2 System layout – Standalone DHW tank
6.3.3 Selecting the volume and desired temperature for the DHW tank
People experience water as hot when its temperature is 40°C. Therefore, the DHW
consumption is always expressed as equivalent hot water volume at 40°C.
However, you can set the DHW tank temperature at a higher temperature
(example: 53°C), which is then mixed with cold water (example: 15°C).
Selecting the volume and desired temperature for the DHW tank consists of:
1
Determining the DHW consumption (equivalent hot water volume at 40°C).
2
Determining the volume and desired temperature for the DHW tank.
Determining the DHW consumption
Answer the following questions and calculate the DHW consumption (equivalent
hot water volume at 40°C) using typical water volumes: