7/10
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Installer setting at variance with
default value
Field settings table
9.I
[1-09]
R/W
[9-03]~[9-02]°C, step: 1°C
18°C (*3)
9.I
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
9.I
[1-0B]
R/W
3~10°C, step: 1°C
5°C
9.I
[1-0C]
R/W
3~10°C, step: 1°C
5°C
9.I
[1-0D]
R/W
3~10°C, step: 1°C
5°C (*3)
9.I
[1-0E]
R/W
3~10°C, step: 1°C
5°C (*3)
9.I
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
9.I
[2-01]
R/W
0: No
1: Yes
9.I
[2-02]
R/W
0~23 hour, step: 1 hour
1
9.I
[2-03]
R/W
60°C
9.I
[2-04]
R/W
40~60 min, step: 5 min
40 min
9.I
[2-05]
R/W
4~16°C, step: 1°C
8°C (*3)
9.I
[2-06]
R/W
0: Disabled
1: Enabled
9.I
[2-09]
R/W
-5~5°C, step: 0,5°C
0°C
9.I
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
9.I
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
9.I
[2-0C]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.I
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.I
[2-0E]
R/W
20~50 A, step: 1 A
50 A
9.I
[3-00]
R/W
0: No
1: Yes
9.I
[3-01]
0
9.I
[3-02]
1
9.I
[3-03]
4
9.I
[3-04]
2
9.I
[3-05]
1
9.I
[3-06]
R/W
18~30°C, step: 0,5°C
30°C
9.I
[3-07]
R/W
12~18°C, step: 0,5°C
12°C
9.I
[3-08]
R/W
25~35°C, step: 0,5°C
35°C (*3)
9.I
[3-09]
R/W
15~25°C, step: 0,5°C
15°C (*3)
9.I
[4-00]
R/W
0: Disabled
1: Enabled
2: Only DHW
9.I
[4-01]
R/W
0: None
1: BSH
2: BUH
9.I
[4-02]
R/W
14~35°C, step: 1°C
35°C
9.I
[4-03]
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
9.I
[4-04]
R/O
0: Intermittent
9.I
[4-05]
0
9.I
[4-06]
R/W
0: Manual
1: Automatic
9.I
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
9.I
[4-09]
R/W
0: Current
1: Power
9.I
[4-0A]
R/W
1: 1/1+2 (*1) (*2)
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.I
[4-0B]
R/W
1~10°C, step: 0,5°C
1°C (*3)
9.I
[4-0D]
R/W
1~10°C, step: 0,5°C
3°C (*3)
9.I
[5-00]
R/W
0: No
1: Yes
9.I
[5-01]
R/W
-15~35°C, step: 1°C
0°C
9.I
[5-02]
R/W
0: Disabled
1: Enabled
9.I
[5-03]
R/W
-15~35°C, step: 1°C
0°C
9.I
[5-04]
R/W
0~20°C, step: 1°C
10°C
What is the maximum allowed current over the heatpump ?
What is the desired delta T in heating for the additional zone?
--
--
--
What is the maximum desired room temperature in heating?
What is the averaging time for the outdoor temp?
Which electric heater has priority?
Which power limitation mode is required on the system?
Which power limitation type is required?
--
Emergency
Operation permission of the booster heater.
Below which outdoor temperature is heating allowed?
Water pipe freeze prevention
When should the disinfection function be executed?
Backup heater configuration
Equilibrium: Deactivate backup heater (or external backup heat source in case of a
bivalent system) above the equilibrium temperature for space heating?
Should the disinfection function be executed?
When should the disinfection function start?
What is the mimimum desired room temperature in heating?
What is the BUH operation mode?
What emitter type is connected to the main LWT zone?
What emitter type is connected to the additional LWT zone?
How long must the tank temperature be maintained?
Room antifrost temperature
Room frost protection
Adjust the offset on the measured room temperature
Adjust the offset on the measured room temperature
What is the required offset on the measured outdoor temp.?
What is the equilibrium temperature for the building?
Space heating priority.
Space heating priority temperature.
Set point correction for domestic hot water temperature.
Automatic cooling/heating changeover hysteresis.
--
Is auto restart of the unit allowed?
--
What is the disinfection target temperature?
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
Automatic cooling/heating changeover offset.
What is the maximum desired room temperature in cooling?
What is the minimum desired room temperature in cooling?
What is the desired delta T in cooling for the main zone?
What is the desired delta T in cooling for the additional zone?
What is the desired delta T in heating for the main zone?
(*1) *6V_(*2) *9W_
(*3) + EKHVCONV2_
(*4) EAVZ16S18*_(*5) EAVZ16S23*
(#) Setting is not applicable for this unit.