13
|
Maintenance and service
Installer reference guide
167
EPGA11~16DAV3(7) + EA23DA6V(7)+9W
Daikin Altherma 3 H F
4P556075-1A – 2021.09
▪
Pressure relief valve of the domestic hot water tank
▪
Switch box
▪
Descaling
▪
Chemical disinfection
Water pressure
Keep water pressure above 1 bar. If it is lower, add water.
Water filters
Clean the water filters.
NOTICE
Handle the water filters with care. Do NOT use excessive force when you reinsert the
water filters so as NOT to damage the water filters mesh.
1
3
2
5
4
Magnetic filter/dirt separator
b
a
c
d
a
Screw connection
b
Magnetic sleeve
c
Drain valve
d
Drain cap
The yearly maintenance of the magnetic filter/dirt separator consists of:
▪
Checking if both parts of the magnetic filter/dirt separator are still screwed
tight (a).
▪
Emptying the dirt separator as follows:
1
Take off the magnetic sleeve (b).
2
Unscrew the drain cap (d).
3
Connect a drain hose to the bottom of the water filter so that the water and
dirt can be collected in a suitable container (bottle, sink...).
4
Open the drain valve for a couple of seconds (c).
Result:
Water and dirt will come out.
5
Close the drain valve.