SiBE12-908
Troubleshooting
Service Diagnosis
158
Troubleshooting
(R9452)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check indoor unit also, because a communication circuit fault
may be caused by the problem related to the indoor unit.
Rated voltage?
YES
NO
Rectify the power supply.
Check supply voltage
Replace the varistor.
Replace the fuse.
Check the varistor on the outdoor
unit PCB
Is it damaged?
YES
NO
NO
YES
Check the fuse on the outdoor
unit PCB
Does it have continuity?
Check the thermal fuse on the
terminal board
Does it have continuity?
Check +5V and GND on the
outdoor unit PCB
YES
NO
Power on again
Wait more than 10 sec.
5 V±0.5 V
NO
YES
Continued to the next page
1
Check the terminal board
connecting wire for proper
connection
Firmly connected?
NO
YES
Replace the thermal fuse
on the terminal board.
Reconnect properly.
Replace the terminal board.
Replace the thermal fuse
on the terminal board.
Replace the outdoor unit
PCB.