Troubleshooting
SiBE12-908
143
Service Diagnosis
2.25 Position Sensor Abnormality
Remote
Controller Display
H6
Method of
Malfunction
Detection
Startup failure of the compressor is identified by rpm information of the compressor and by
electric component position detector.
Malfunction
Decision
Conditions
When the compressor does not run for 15 seconds after receiving operation start command
The unit shuts down if the fault occurs 16 times
Clear condition: The compressor continuously runs for 11 minutes without fault
Supposed
Causes
Detection error due to disconnection of compressor harness
Startup failure due to defective compressor
Startup failure due to defective outdoor unit PCB
Startup failure due to closed stop valve
Input voltage fault