Main Functions
SiBE12-908
15
Function and Control
Inverter Features
The inverter provides the following features:
The regulating capacity can be changed according to the changes in the outdoor air
temperature and cooling / heating load.
Quick heating and quick cooling
The compressor rotational speed is increased when starting the heating (or cooling). This
enables a quick set temperature.
Even during extreme cold weather, the high capacity is achieved. It is maintained even when
the outdoor air temperature is 2°C.
Comfortable air conditioning
A detailed adjustment is integrated to ensure a fixed room temperature. It is possible to air
condition with a small room temperature variation.
Energy saving heating and cooling
Once the set temperature is reached, the energy saving operation enables to maintain the
room temperature at low power.
Frequency Limits
The following table shows the functions that define the minimum and maximum frequency:
Forced Cooling
Operation
For more information, refer to “Forced operation mode” on page 53.
(R1187)
Air discharge
temperature
45°C
Start
inverter
normal heat pump
60
120
300
seconds
Frequency limits
Limited during the activation of following functions
Low
Four way valve operation compensation. Refer to page 43.
High
Discharge pipe temperature control. Refer to page 44.
Input current control. Refer to page 45.
Compressor protection function. Refer to page 44.
Heating peak-cut control. Refer to page 46.
Freeze-up protection control. Refer to page 45.
Defrost control. Refer to page 47.