Troubleshooting
SiBE12-908
115
Service Diagnosis
Troubleshooting
Check No.29
Refer to P.179
(R9432)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the capacity of
safety breaker as
specified?
NO
[Power supply]
YES
NO
NO
NO
NO
NO
Does the earth leakage
breaker work?
Is it an exclusive circuit?
Is the size of wire for
the exclusive circuit as
specified?
YES
NO
YES
YES
YES
YES
YES
[Installation]
Is the supply voltage
within the rated voltage
±10%?
Is there required
installation space? (Isn't it
short circuited?)
Is the size of the
connecting wire as
specified?
Check No. 29
Short circuit check
Is it OK?
YES
NO
· Air is mixed in.
· Overfilling of refrigerant is
supposed.
Check No. 29
Short circuit check
Remove the fan motors or the
four way valve coil and check.
Is it OK?
YES
NO
Replace the safety breaker
to a specified one.
Increase the set value of
the earth leakage current
on the breaker (or replace
the breaker).
Use the exclusive circuit.
Replace the wire to a
specified one by referring to
the electric wire distance
described in the installation
manual.
Contact with an electric
power company.
Secure the required space.
Replace the wire to the
specified one.
Replace the outdoor unit
PCB.
Replace the fan motor or
the four way valve coil.
Conduct vacuum drying, fill
the refrigerant of specified
volume.