background image

SQLC-216-212

 

 

35 

 

 

10 Description of functions 

10.1 Contact output 

  (1)Contact function 
      ・Contact output can be set to pulse output or alarm output. 
        【Seting】No.111  Contact output 1 function 

No.114  Contact output 2 function 

  (2)Alarm output 
      ・Assign the output (output 1, output 2, output 1 and output 2)  for each alarm setting. 
        (All of the alarm, can be output in the OR to contact output) 
        【Setting】No.122  Current, upper 1 output                 No.124  Current, upper 2 output 
                   No.126  Current, lower output 
                   No.133  Demand current, upper 1 output          No.135  Demand current, upper 2 output 
                   No.143  Demand power, upper 1 output            No.145  Demand power, upper 2 output 
                   No.152  Leakage sensitivity current 1 output    No.154  Leakage sensitivity current 2 output 
 

10.2 Inrush current mask function 

・According to the a inrush current (such as a transformer a inrush current and motor starting current), it 

prevents the update of the alarm output and maximum value. 

・Between the current value exceeds the a inrush current mask level of the mask time, the detection and the  

maximum value of each upper alarm does not update. 

        【Setting】No.161 Inrush current mask level 
                   No.162 Inrush current mask time 
 

 
 
 
 
 
 
 
 
 
 

10.3 Power flow measurement 

      ・Set power flow measurement with an awareness of the transmission / receiving of reactive power and power factor. 
        【Setting】No.261 Power flow measurement 

General measurement (OFF) 

:Displays the polarity (LAG / LEAD) supplied from the power system side. (Both receiving and transmission) 

Power flow measurement (ON) 

:Displays the polarity (LAG / LEAD) supplied from the power system side. (At receiving) 
  Displays the polarity (LAG / LEAD) supplied from the power generation side. (At transmission) 

 
 
 
 
 
 
 
 
 
 

 
 
 
 
 

LEAD      LAG 

LEAD      LAG 

270°                      90° 

0° 

180° 

Reference V 

Receiving (Power purchase) 

Polarity display of the general measurement 

 (OFF) setting

】 

Current of  
lagging phase 

Current of  
leading phase 

Transmission (Power selling) 

Polarity 
supplied from 
the power 
system side 

LEAD      LAG 

LAG      LEAD 

270°                      90° 

0° 

180° 

Reference V 

Receiving (Power purchase) 

Polarity display of power flow measurement 
(ON) setting

】 

Current of 
lagging phase 

Current of  
leading phase 

Transmission (Power selling) 

Leading 
current 

Lagging 
current 

Polarity 
supplied from 
the power 
system side 

Polarity 
supplied from 
the generator 
side 

Inrush current mask time 

Inrush current mask level 

Current value 

Time 

In this range, the detection and the
maximum value does not update. 

Upper detection value 

Содержание SQLC-72L

Страница 1: ...SQLC 216 212 INSTRUCTION MANUAL DETAILED VERSION POWER LINE SUPER MULTI METER SQLC 72L...

Страница 2: ...ion and Screen 11 6 Display mode 12 6 1 Measurement display 12 6 2 Instant measurement display mode 13 6 3 Maximum value Minimum value display mode 14 6 4 Reset 14 6 5 Setting value display mode 15 7...

Страница 3: ...nt Use unsuitable size electric wire which may lead to a fire Please carry out coating removal of a covering electric wire by reasonable length If covering removal is too long there is a possibility o...

Страница 4: ...e date of delivery Warranty scope In the state of the normal use of product specification within the range according to this instruction manual the trouble within the warranty period performs exchange...

Страница 5: ...white backlight Wiring can be confirmed by the test function Screw less spring type terminal block the adoption Wiring man hours can be reduced RS485 Communication output MODBUS RTU Alarm output Pulse...

Страница 6: ...TRUMENTS Co Ltd 5A CTF 5A 7 9 25 3 42 41 3 10 38 5 33 50A CTF 50A 25 5 42 9 5 10 28 6 23 48 100A CTF 100A 14 5 46 30 5 55 16 37 5 29 5 200A CTF 200A 24 52 5 35 5 76 24 55 5 45 400A CTF 400A 35 5 18 5...

Страница 7: ...8 9 3 Mounting pitch 76 1 7 20 Terminal cover 17 5 9 5 2 2 2 200A OTG LA42 Terminal cover 25 17 107 42 Mounting pitch 97 109 88 9 3 11 5 2 400A OTG LA68 Mounting pitch 143 118 68 136 131 31 Terminal c...

Страница 8: ...ole Install as shown in the figure below Connection of current sensor Remove the fixing hooks and open the movable core Please check the mounting direction of the current sensor Symbol Power supply si...

Страница 9: ...insulating collar Ferrule without insulating collar Twin ferrule with insulating collar In case of flexible stranded wire please be careful not to loosen the wire There is a rod terminal as a prevent...

Страница 10: ...5 mm Insert the screwdriver to screwdriver insertion slot open the spring To insert the wire to the wire insertion slot Pull out the screwdriver close the spring Recommended screwdriver Cutting edge...

Страница 11: ...21 19 23 K CURRENT SENSOR L ZCT CT K L N 31 CURRENT SENSOR INPUT COM CONTACT OUTPUT 1 CONTROL INPUT AUX SUPPLY CONTACT OUTPUT 2 10 25 26 27 3 4 2 1 6 8 5 7 9 28 29 30 14 12 16 13 11 15 20 18 22 19 17...

Страница 12: ...tion resistor for the communication output please use at the end of equipment Please connect the termination resistor between the terminals of communication output Note In case of the high voltage cir...

Страница 13: ...play Phase Line Average value AVG SET Pressing for more than 3 second Switch to setting mode 1 SET and RESET Pressing for more than 3 second Switch to setting mode 2 SET and DISPLAY Pressing for more...

Страница 14: ...switched in the following order P Q Wh Wh varh LAG varh LEAD varh LAG varh LEAD OFF 3 Switching of phase line average value AVG display By pressing the DISPLAY switch the phase line display of the mai...

Страница 15: ...When the carry out this operation in the maximum minimum measurement display mode the maximum value minimum value of measurement element in display is reset Always instant measurement display mode pl...

Страница 16: ...ing value display mode Pressing the switch in the setting value display mode switching the voltage setting and current setting If you press the DISPLAY switch or do not operate any switches for over 1...

Страница 17: ...put RESET 127 0A detection exclude Demand current detection 131 Demand current interval RESET 132 Demand current upper 1 RESET 133 Demand current upper 1 output RESET 134 Demand current upper 2 RESET...

Страница 18: ...122 124 126 Current upper 1 output Current upper 2 output Current lower output Set output allocation of upper detection 1 and upper detection 2 and lower detection Setting value is selecting in the To...

Страница 19: ...nd power upper 1 Demand power upper 2 Set detection value of the upper detection 1 and the upper detection 2 of demand power Setting value is selecting in the To update the setting value in the SET 14...

Страница 20: ...rrent mask level Set detection value of the inrush current Setting value is selecting in the To update the setting value in the SET 162 Inrush current mask time Set mask time after the inrush current...

Страница 21: ...1 Display mode DISPLAY SET and RESET 3 seconds Setting mode 2 Circuit 211 Wiring type RESET 212 Phase display RESET 213 Number of input CT RESET 214 Leakage measurement ON OFF RESET and RESET and RESE...

Страница 22: ...pdate the setting value in the SET Note In case of use in the direct connection The primary rated voltage setting and the secondary rated voltage setting please set to the same value 222 Primary rated...

Страница 23: ...4 wire 3 1 phase 3 wire 2 1 phase 2 wire 1 Note 11 Units of display and communication data of the integrated active energy is MWh Mvarh Note 12 The liquid crystal is 0001kWh display Note 13 The liqui...

Страница 24: ...ut function Set function of the control input Setting value is selecting in the To update the setting value in the SET Function of control input Alarm reset rES 1 Maximum Minimum value reset rES 2 All...

Страница 25: ...lue is selecting in the To update the setting value in the SET 7 Power flow No Setting item Contents of setting 261 Power flow measurement Set power flow measurement with an awareness of the transmiss...

Страница 26: ...e SET 3 seconds to reset all of the integrated value Wh Wh varh LAG varh LAG varh LEAD varh LEAD 273 Setting management No If the setting by the communication has been made to display the setting mana...

Страница 27: ...ation of pulse output and alarm output The operation of contact output 1 can be check by the 321 The operation of contact output 2 can be check by the 322 Pulse output 0FF oFF Pulse output OFF ON on P...

Страница 28: ...and press the SET switch the measurement data of all measuring elements have been changed Numerical data 0 measurement data 0 50 measurement data 5000 100 measurement data 10000 SEq sequence number P...

Страница 29: ...RADING CO LTD M BM SM series low voltage FUJI ELECTRIC CO LTD Circuit Breaker BW125 Control input DI Non voltage contact input 1ch Contact capacity 24 V DC Approx 10 mA Output Communication output MOD...

Страница 30: ...tions Power factor PF PF PF PF1 PF2 PF3 1 5 is displayed at the case of low input Frequency f 0 5 0 0Hz is displayed at the case of low input Leakage current Io 2 5 19 0A is displayed when an input is...

Страница 31: ...min 30 min The response time for time limit 0 second is less than 1 second Demand power Contact output Output 2ch Output form Optical MOS FET relay Normally open contact Contact capacity 20 30 V DC 70...

Страница 32: ...on setting Setting to the following function is possible Function Alarm output reset All the outputs of an alarm output when a return method is manual return are reset Maximum minimum value reset All...

Страница 33: ...als Other circuit grounding Damped oscillatory wave immunity test IEC61000 4 12 Peak voltage 2 5 kV frequency 1 MHz 10 Add 3 times for 30 seconds Error Within 10 And malfunction and communication stop...

Страница 34: ...0100 Active power Demand power Reactive power rated power 0 rated power Rated power kW VT ratio CT ratio VT ratio Primary rated voltage 110 CT ratio Primary rated current 5 Less than 0 5 of the rated...

Страница 35: ...rate 0 01 k 125 Current lower OFF 233 Pulse output 2 element OFF 126 Current lower output OFF 234 Pulse output 2 rate 0 01 k 127 0A detection exclude ON Exclude detection 241 Control input function 1...

Страница 36: ...h current mask level No 162 Inrush current mask time 10 3 Power flow measurement Set power flow measurement with an awareness of the transmission receiving of reactive power and power factor Setting N...

Страница 37: ...ree space 100 MB or more If the Microsoft NET Framework 4 5 is not installed free space 300 MB or more Display Resolution 1024 768 or higher High Color 65536 colors or higher Interface RS 232C or USB...

Страница 38: ...tput Voltage and current primary and secondary rating setting is wrong Please check the setting of current sensor and secondary voltage and primary voltage and primary current Pulse rate setting is wr...

Страница 39: ...0 k 2700 k 40 00 M 36 36 M 33 45 M 30 00 M 25 09 M 24 00 M 20 00 M 12 00 M 6000 k 4000 k 3000 k 48 00 M 43 64 M 40 15 M 36 00 M 30 11 M 28 80 M 24 00 M 14 40 M 7200 k 4800 k 3600 k 60 00 M 54 55 M 50...

Страница 40: ...k 1129 k 785 5 k 752 7 k 720 0 k 679 1 k 654 5 k 621 8 k 360 0 k 180 0 k 2000 k 1800 k 1600 k 1255 k 872 7 k 836 4 k 800 0 k 754 5 k 727 3 k 690 9 k 400 0 k 200 0 k 2400 k 2160 k 1920 k 1505 k 1047 k...

Страница 41: ...0 k 1500 k 1600 k 1800 k 2000 k 2400 k 3000 k 4000 k 6000 k 110 0V 30000A 6000A 12000A 15000A 20000A 3000A 4000A 900A 5000A 7500A 1200A 1500A 2000A 2500A 1600A 1800A 4500A 3500A 750A 800A 200A 250A 30...

Страница 42: ...50 k 20 00 M 18 18 M 16 73 M 15 00 M 12 55 M 12 00 M 10 00 M 6000 k 3000 k 2000 k 1500 k 24 00 M 21 82 M 20 07 M 18 00 M 15 05 M 14 40 M 12 00 M 7200 k 3600 k 2400 k 1800 k 30 00 M 27 27 M 25 09 M 22...

Страница 43: ...0 00 k 1000 k 900 0 k 800 0 k 627 3 k 436 4 k 418 2 k 400 0 k 377 3 k 363 6 k 345 5 k 200 0 k 100 0 k 1200 k 1080 k 960 0 k 752 7 k 523 6 k 501 8 k 480 0 k 452 7 k 436 4 k 414 5 k 240 0 k 120 0 k 1500...

Страница 44: ...3 Hitotsuya 1 chome Adachi ku Tokyo 121 8639 JAPAN TEL 81 3 3885 2411 Fax 81 3 3858 3966 Kyoto Office 1 19 Ichinobe Nishikawahara Jyoyou shi Kyoto 610 0114 JAPAN TEL 81 774 55 1391 Fax 81 774 54 1353...

Отзывы: