SQLC-216-212
24
(6) Communication
No.
Setting item
Contents of setting
251
Address
Set address of the device in
MODBUS communication output.
Setting value is selecting in the【+】
【-】.
To update the setting value in the【SET】.
252
Bit rate
Set bit rate (bps) of the MODBUS
communication output.
Setting value is selecting in the
【+】
【-】.
To update the setting value in the
【SET】.
253
Parity
Set parity of the MODBUS communication output.
Setting value is selecting in the
【+】
【-】.
To update the setting value in the
【SET】.
254
Stop bit
Set stop bit of the MODBUS communication output.
Setting value is selecting in the
【+】
【-】.
To update the setting value in the
【SET】.
(7) Power flow
No.
Setting item
Contents of setting
261
Power flow
measurement
Set power flow measurement with an awareness of the
transmission / receiving of reactive power and power factor.
Setting value is selecting
in the【+】【-】.
To update the setting value
in the【SET】.
262
Reactive power
calculation
method
Set reactive power calculation method.
Setting value is selecting in the
【+】
【-】. To update the setting
value in the【SET】.
Stop bit
1 bit
1
2 bit
2
Parity
Nothing
-
Even number
E
Odd number
o
Bit rate
4800bps
4.80k
9600bps
9.60k
19200bps
19.20k
38400bps
38.40k
Address
1 ...247
Rreactive power
calculation method
Q=UIsinφ
0
Q=√(S
2
-P
2
)
1
Power flow measurement
General measurement
oFF
Power flow measurement
on