SQLC-216-212
11
4.2 High-voltage circuit
(
4
)
■ The use example of high-voltage circuit, 3 phase 3 wire(2VT2CT)
AUX.SUPPLY
CONTACT OUTPUT 1
CONTACT OUTPUT 2
CONTROL INPUT
-
~
( )
~
( )
+
25
26
27
28
29
30
31
SENSOR
CURRENT
MODBUS
(INPUT)
(COM)
(-)
(-)
(+)
(+)
2
1
4
6
3
5
10
8
7
12
9
11
LOAD
( )
3
K
K
L
15
16
14
13
18
17
21
22
20
19
24
23
K
L
L
L
CT
K
U
U V
L1
VT
V
L3
L2
Note(
1
) In case of the low-voltage circuit (600 V or less), the secondary grounding of VT / CT is not required.
In case of the 110V / 220V / 440V direct input, VT is not required.
Note(
2
) When using with a circuit of 600 A or more, please connect the current sensor of the 5 A rated the
(CTF-5A) on the secondary side of the instrument for the current transformer (secondary 5 A).
Note(
3
) Communication output terminal (7-8, 9-10, 11-12 ,13-14) are connected internally respectively.
In case of the daisy chain, please connect in accordance with the 10 pages figure.
Termination resistor for the communication output, please use at the end of equipment.
Please connect the termination resistor between the terminals (+)(-) of communication output.
Note(
4
) In case of the high-voltage circuit, using instrument transformers (VT), and instrument for the
current transformer (CT) of secondary rated 5 A, please ground the secondary side.
Current sensor in the secondary of the current transformer, please connect the current sensor (CTF-5A)
of 5A rating.
5 Operation and Screen
Current sensor connection diagram of circuit
of 600A or more and high-voltage circuit. (
2
)
Current transformer of
secondary output 5A.
Current sensor
(5A rating:CTF-5A)
Setting
number
Setting
number
For more information on each mode,
please refer to each page.
New
setting
Current
setting
New
setting
Current
setting
Test
number
Setting mode 2
SET
3 seconds
Start screen
Display mode
(Measurement
display)
Display for 2
seconds
DISPLAY
POWER ON
Not operated for 10 minutes
16 pages
12 pages
SET and RESET
3 seconds
SET and DISPLAY
3 seconds
DISPLAY
DISPLAY
20 pages
26 pages
Setting mode 1
Test mode