SQLC-216-212
13
6.2 Instant measurement display mode
(1) Switching of main-monitor display element
Press the【SET】
switch, to display the【▲】
(operation effective display).
Then by pressing the【+】
【-】
switch the display elements of the main-monitor.
【 Voltage (U) display 】 【 Current (I) display 】 【 Demand current (Id) display 】
Measuring element is switched in the following order.
U ⇔ I ⇔ Id ⇔ P ⇔ Pd ⇔ Q ⇔ S ⇔ PF ⇔ f ⇔ Io ⇔ OFF
(2) Switching of the sub-monitor display element
Press the【SET】
switch, to display the【▼】
(operation effective display).
Then by pressing the【+】
【-】
switch the display elements of the sub-monitor.
【 Active power (P) display 】 【Reactive power (Q) display】 【Receiving active energy (Wh) display】
Measuring element is switched in the following order.
P ⇔ Q ⇔ Wh ⇔ -Wh ⇔ varh(LAG) ⇔ varh(LEAD) ⇔ -varh(LAG) ⇔ -varh(LEAD) ⇔ OFF
(3) Switching of phase (line) / average value (AVG) display
By pressing the【DISPLAY】
switch the phase (line) display of the main-monitor.
Measuring element is switched in the following order.
Measurement element (1,2,3,N:Phase, Σ:Total)
3 phase 3 wire
1 phase 3 wire
3 phase 4 wire
Voltage
U(L1-2) ⇔ U(L2-3) ⇔
U(L3-1) ⇔ U(L-L AVG)
U(L1-N) ⇔ U(L3-N) ⇔
U(L1-3) ⇔ U(L-N AVG)
U(L1-N) ⇔ U(L2-N) ⇔ U(L3-N) ⇔ U(L1-2) ⇔
U(L2-3) ⇔ U(L3-1) ⇔ U(L-N AVG) ⇔ U(L-L AVG)
Current,
Demand current
I(L1) ⇔ I(L2) ⇔
I(L3) ⇔ I(AVG)
I(L1) ⇔ I(L3) ⇔
I(N) ⇔ I(AVG)
I(L1) ⇔ I(L2) ⇔ I(L3) ⇔ I(N) ⇔ I(AVG)
Active power,
Demand active power
―
―
P(Σ) ⇔ P(L1) ⇔ P(L2) ⇔ P(L3)
Reactive power
―
―
Q(Σ) ⇔ Q(L1) ⇔ Q(L2) ⇔ Q(L3)
Apparent power
―
―
S(Σ) ⇔ S(L1) ⇔ S(L2) ⇔ S(L3)
Power factor
―
―
PF(Σ) ⇔ PF(L1) ⇔ PF(L2) ⇔ PF(L3)
Display of phase / line, can be switched in the settings.
Setting
L123N
RSTN
UVWN
Phase, line
display
L1
R
U
L2
S
V
L3
T
W
N
N
N
+
-
+
-
+
-
+
-
DISPLAY
DISPLAY