User’s Manual
27
Command
Output time
020
①
001
③
②
90
Table 3-15
Output time
Number Description
1
The encoding address. The command operation means configuring output time for
relay.
2
Relay.
ARC9 series: 001-256.
ARC2 series: 001-084.
3
Output time.
The relay output time can be set between 90 seconds to 900 seconds.
Example
The relay output time is set as 90 seconds.
The admin user enters 02000190 under programming mode.
Press
Enter
.
3.6.4.2
Module Type
Description
Configure relay output module type as needed.
Command
Module type
021
①
005
③
②