LSC 44-M4
99.823.35 1.2/06/09
Emergeny Power Accumulators
LSC-System for ventilation purposes as well
Attention
-
-
Wrong polarization will result in damages both at
accumulator unit and control panel.
-
Accumulators are maintenance-free and
Only accumulators authorized by the
manufacturer are permitted to use.
Date of installation must be noted down on
accumulators.
must
be exchanged every 4 years.
Putting on of
Mains Supply
Connection
The device is equipped with 2 emergency power
accumulators à 12V, which will be connected in
series with a bridge (2x12V=24V)
Putting on of the mains supply will be effected via
terminals L1, N and PE.
It will be protected by a fuse for feeble currents.
Check distribution voltage after connecting.
The system facilitates to use the SHEV-system for
ventilation purposes as well. This will be effected
via ventilation button or a floating contact in neutral
position of another control system. A time-
controlled automatic closing of the SHEV-system
can be programmed, if required.
DIP-Switch 1 on ON
= OPEN-running time limitation
DIP-Switch 2 on ON
= Ventilation time limitation
Using a potentiometer, running time in Open direction can
be limited. If the vent button is actuated in Open direction,
The drive will run open as long as the running time is set.
Using a potentiometer, ventilation time can be set.
Drives will automatically close again, after the adjusted
time has expired.
Automatic ventilation can be optionally realized via timer.
The possibility of ventilation will be automatically
blocked in any kind of malfunction.
Possibility of selecting different variants via
codification of the control panel.
Following ventilation functions can be set with DIP-
switch S1 on the motherboard of RZN 44004-M for
example: