5.7
1 2 3 4 5 6 7 8
ON
SAB
1 2 3 4 5 6 7 8
ON
SAB
1 2 3 4
ON SAB
1 2 3 4
ON SAB
29/48
LSC 44-M4
99.823.35 1.2/06/09
Switch 1 on ON =
OPEN - running time limitation
If Dip switch 1 is switched on ON, the OPEN-running time limitation can
Using a potentiometer, running time in Open direction can be
Limited. If the vent button is actuated in Open direction, the drive
will run open as long as the running time is set.
Using a potentiometer, ventilation time can be set. Drives will
automatically close again, after the adjusted time has expired.
Switch 2 on ON =
Ventilation time limitation
Switch 3 on ON =
OPEN - retriggering
Only possible in conjunction with group-DIP-switches 4 = ON
(storage operation in CLOSED-direction)!
Only possible in conjunction with group-DIP-switch 1 = ON
(OPEN-running time limitation)!
be retriggered again.
Switch 4 on ON =
Storage operation in CLOSED-direction
Switch 4 on OFF =
Key operation in CLOSED-direction
Switch 5 on ON =
Storage operation in OPEN-direction
Switch 5 on OFF =
Key operation in OPEN-direction
Switch 6 on ON =
Group CLOSED in case of alarm
Switch 7 on ON =
Group fault on alarm
smoke vent
opens
group fault
Switch 8 on ON =
Alarm re-clocking
Press ventilating button
1x shortly > the drive will be closing up to its
final position
The drives will be closing only so long as the ventilating button
is pressed.
Press ventilating button
1x shortly > the drive will run open up to its
final position.
The drives will run open only so long as the ventilating button
is pressed.
The group will be closing in case of alarm!
The control panel will be switched on alarm, that means, the
in case of
(e.g. in case of an interrupted control line).
The smoke vent is triggered for a duration of 30 minutes in intervals of
2 minutes according to VdS 2581.
.
See page 10 about this
min
15
2
45
30
sec
20
2
60
40
Codification of Group 1 and 2
Following functionings can be set with
on motherboard.
DIP switch S2/ S4