X.x
6.6
Ø 90
Ø 84
Ø 42
70
44/48
LSC 44-M4
99.823.35 1.2/06/09
Operating voltage
: 8 V - 28 VDC
Rest current
Alarm current
: 9.2mA ±1 mA
Alarm display
: LED rot
Storing temperature
: -25 to +75 °C
Working temperature : -20 to +72 °C
Protective system
: <55μA
: IP40
(with PG-basel IP42)
Housing
: ABS synthetic, white
Technical design
: EN 54, part 7
VdS approval
: G29226 (O-1362)
If this LED lightens, release has been taken place
through
automatic detector.
Release will be reset via “Closed-Reset”-button in
a SHEV-button.
this
- Fasten detector with 2 screws
- Close cable bushings, which are not used
- A protective cap is available for avoiding dirt
accumulation during construction
(see figure)
The detector consists of the base with the
connections and the detector upper part with
evaluation unit. Detector base and upper part are
connected via a bajonet catch (a quarter turning).
The smoke detector must be horizontally placed at
the highest point underneath the ceiling in proximity
of the landing entrance on the first main evacuation
level.
See also instruction for use of FO 1362
Fire detector FO 1362