3.5
3.6
LSC 44-M4
13/48
LSC 44-M4
99.823.35 1.2/06/09
Cable for D+H Smoke and Heat Vent Systems
The smoke vent control panel is designed for
opening smoke vent devices, which operate by
thermal ascending force and by automatic fire
recognition devices (thermal detector, smoke
detector), and they release either self-acting or
manual by smoke detectors at an early stage of a
fire, and remain in opened position without further
power consumption. In these cases, functioning
preservation of the electrical line system is required
only at an early stage of fire. Protected wiring is
required with protection against mechanical
damages according to DIN 18232 section 2.7.2.4.
Cable from the smoke vent control panel to
connection of drive (drive lines have a monitoring
wire, in which fire recognition devices (thermal
maximal detector e.g. THE) can be looped-in):
- Safety line, with functional conservation
... E30, according to DIN 4102* or standard
guidelines for line systems MLAR.
Control Cable (Group):
Detector Cables (Line):
Cables through areas not monitored:
The detector cables are monitored for short circuit
and for break.
The opening device is automatically triggered and
opens up in case of fault, when DIP-switch 3 is on
ON.
Smoke vent button cable and cable of automatic
detectors:
-
weak current sheathed flexible cable YR 6 x 0.8
or
-
house wiring cable IY(ST)Y 4 x 2 x 0.6
An increased time of functioning of the cable can be
required, when drive lines are installed through
building parts, which are not monitored.
-
Safety line with functional conservation
... E90, according to DIN 4102* or standard
guidelines for line systems MLAR.
(see supplementary sheet 1 to DIN VDE 0108)
* Notice: No type designation is given for these
cables, because of a large variety on the market.
Please consult your D+H distributor about these.
plain cable length (m) x number of drives
80 **
Line lengths and Cross sections
Number of wires and cross-sections indicated, refer to required lines only. In case of using a line with
earthed conductor (green/ yellow), this one will not be counted in and must not be wired.
*
**
connect in parallel 2 wires for each drive line
only valid for drives with 1A actuating current. Use „160“ for drives with 0,5A actuating current
and „230“ for drives with 0,35A actuating current.
cross section (mm²) =
Type
drive
0,5A
1
2
3
4
5
6
7
8
1A
1
2
3
4
3 x 1,5mm²
240
120
80
60
48
40
34
30
3 x 2,5mm²
400
200
130
100
80
65
55
50
5 x 2,5mm²
800
400
260
200
160
130
110
100
Содержание LSC-M Series
Страница 1: ...Instruction for use Lift Smoke Control LSC M System for Lift Shaft and Staircase Smoke Vent...
Страница 2: ......
Страница 51: ......