background image

D200-09-00 

I56-0058-004R

7251 intelligent Laser Smoke Sensor

inStaLLatiOn and maintenanCe inStrUCtiOnS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495 

www.systemsensor.com

BeFOre inStaLLing

This  sensor  must  be  installed  in  compliance  with  the  control  panel  system 
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when 
installed in compliance with the National Fire Protection Association (NFPA); 
see NFPA 72.

generaL deSCriPtiOn

Model  7251  is  a  plug-in  type  smoke  sensor  that  uses  a  laser  based  sensing 
chamber.  The  sensor  uses  analog-addressable  communications  to  transmit 
smoke  density  and  other  information  to  the  control  panel.  Rotary-decade 
switches are provided for setting the sensor’s address. Two LEDs on the sensor 
are controlled by the panel to indicate sensor status. An output is provided for 
connection to an optional remote LED annunciator (P/N RA400Z). 

This detector requires compatible addressable communications to function 
properly. Connect this sensor to listed-compatible control panels only.

SPaCing

System Sensor recommends spacing sensors in compliance with NFPA 72. In 
low air flow applications with smooth ceilings, space sensors 30 feet apart. For 
specific information regarding sensor spacing, placement, and special applica-
tions, refer to NFPA 72 or the System Sensor 

Guide For Proper Use of System 

Smoke Detectors

, available from System Sensor (P/N I56-407-XX).

Wiring inStrUCtiOnS

All wiring must be installed in compliance with the National Electrical Code, 
applicable local codes, and any special requirements of the Authority Having 
Jurisdiction. Proper wire gauges should be used. The installation wires should 
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper  connections  will  prevent  a  system  from  responding  properly  in  the 
event of a fire.

Remove power from the communication line before installing sensors.

All  wiring  must  conform  to  applicable  local  codes,  ordinances,  and  regula-
tions.

1.   Wire the sensor base (supplied separately) per the wiring diagram, see 

Figure 1.

2.  Set the desired address on the sensor address switches, see Figure 2.
3.   Install the sensor into the sensor base. Push the sensor into the base while 

turning it clockwise to secure it in place.

4.   After all sensors have been installed, apply power to the control unit and 

activate the communication line.

5.  Test the sensor(s) as described in the TESTING section of this manual.

SPeCiFiCatiOnS 

Operating Voltage Range: 

15 to 32 VDC

Standby Current: 

330µA @ 24 VDC (one communication every 5 sec. with LED blink enabled)

Max. Alarm Current (LED on:) 

6.5 mA @ 24 VDC

Operating Humidity Range:  

10% to 93% Relative Humidity, noncondensing

Operating Temperature Range: 

0°C to 38°C (32°F to 100°F); U.S.

 

–10°C to 50°C (14°F to 122°F); Europe (this range not evaluated by UL)

Height:  

1.7 inches (43 mm) installed in B210LP Base

Diameter: 

6.1 inches (155 mm) installed in B210LP Base

 

4.1 inches (104 mm) installed in B501 Base

Weight: 

5.0 oz. (142 g)

Additional Bases Available: 

All 200/500 Series bases are compatible.

I56-0058-004R

teSting

Before  testing,  notify  the  proper  authorities  that  the  system  is  undergoing 
maintenance,  and  will  temporarily  be  out  of  service.  Disable  the  system  to 
prevent unwanted alarms.

All sensors must be tested after installation and periodically thereafter. Test-
ing  methods  must  satisfy  the  Authority  Having  Jurisdiction  (AHJ).  Sensors 
offer maximum performance when tested and maintained in compliance with 
NFPA 72. 

The sensor can be tested in the following ways:

A.  Functional: Magnet Test (P/N M02-04-01 or M02-09-00) 
 

 This  sensor  can  be  functionally  tested  with  a  test  magnet.  The 
test  magnet  electronically  simulates  smoke  in  the  sensing  cham-
ber, testing the sensor electronics and connections to the control 
panel.

 

1.   Hold the test magnet in the magnet test area as shown in Figure 3.

 

2.  The sensor should alarm the panel.

 

 Two LEDs on the sensor are controlled by the panel to indicate sen-
sor status. Coded signals, transmitted from the panel, can cause the 
LEDs to blink, latch on, or latch off. Refer to the control panel tech-
nical documentation for sensor LED status operation and expected 
delay to alarm.

B.  Smoke Entry: Aerosol Generator (Gemini 501)
 

 The GEMINI model 501 aerosol generator can be used for smoke 
entry testing. Set the generator to represent 4%/ft. to 5%/ft. ob-
struction as described in the GEMINI 501 manual. Using the bowl 
shaped applicator, apply aerosol until the panel alarms.

A sensor that fails any of these tests should be cleaned as described under 
CLEANING, and retested. If the sensor fials after cleaning, it must be replaced 
and returned for repair.

When testing is complete, restore the system to normal operation and notify 
the proper authorities that the system is back in operation.

CAUTION

Dust covers provide limited protection against airborne dust particles during 
shipping. Dust covers must be removed before the sensors can sense smoke. 
Remove sensors prior to heavy remodeling or construction.

Summary of Contents for 7251

Page 1: ...te the communication line 5 Test the sensor s as described in the TESTING section of this manual Specifications Operating Voltage Range 15 to 32 VDC Standby Current 330µA 24 VDC one communication every 5 sec with LED blink enabled Max Alarm Current LED on 6 5 mA 24 VDC Operating Humidity Range 10 to 93 Relative Humidity noncondensing Operating Temperature Range 0 C to 38 C 32 F to 100 F U S 10 C t...

Page 2: ...r 9 Test the detector as described in TESTING 10 Reconnect disabled circuits 11 Notify the proper authorities that the system is back on line Figure 1 Wiring diagram CAUTION Do not loop wire under terminal 1 or 2 Break wire run to pro vide supervision of connection UL Listed Compatible Control Panel Laser Safety Information This smoke detector does not produce any hazardous laser radiation and is ...

Page 3: ... Test magnet position TENS ONES 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 D N T N I A P T O O T E S T M A G N E T TEST MAGNET PAINTED SURFACE MAGNET TEST MARKER LED STATUS INDICATORS PAINTED SURFACE C0170 00 Figure 4 Sensor assembly SENSOR COVER COVER REMOVAL TABS SCREEN ASSEMBLY SENSING CHAMBER ...

Page 4: ...art 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a ...

Reviews: