Keypad
Display
Fault Name
Cause
Possible Solution
to F1-09
Detection Level) and F1-10
(Overspeed Detection Delay
Time )
Bb
Baseblock
Controller output
interrupted by an
external baseblock
signal
An external baseblock
signal was input via one of
the multi-function input
terminals (S1 to S8)
Check baseblock signal input
timing and external sequence
oH2
Controller Overheat
Warning
Controller Overheat
Warning input via a
multi-function input
terminal (S1to S8 ) when
E1-口口= 40
An overheat warning in
the controller was
triggered by an external
controller
1. Search the controller which
caused the overheat warning.
Remove the cause of the
problem.
2. Reset Controller Overheat
Warning input at the assigned
multi-function input terminal
(S1to S8)
HCA
Current Alarm
Controller current
exceeded the level of
over current warning
(150% of the rated
current)
1. The load is too heavy
2. Deceleration and
acceleration times are too
short
3.The controller is
attempting to run a
greater than the maximum
allowable capacity, or a
special-purpose is being
used
4.The current level went up
because of Speed Search
while attempting to
perform a fault restart or
after a momentary power
loss
1. Reduce the load or use a
controller of higher rating
2. Calculate the torque required
during acceleration and the
inertia
»Take the following steps if the
torque level is not right for the
load
· Increase the settings for
acceleration and deceleration
time (C1-00 to C1-07)
· Use a controller of higher rating
3. Check the capacity
· Make sure the capacity is right
for the controller rating.
4. During a momentary power
loss or an attempt to reset a fault,
the alarm is displayed. However,
there is no need to take any
action because the fault display
will disappear shortly