Parameter
Name
Description
Setting Range
P6-10 Forward Torque
Limit
Sets the torque limits as a percentage of the
Load Rated torque.
Default: 200%
Min.: 0%
Max.: 300%
P6-11 Reverse Torque
Limit
Default: 200%
Min.: 0%
Max.: 300%
P6-12
Forward
Regenerative
Torque Limit
Default: 200%
Min.: 0%
Max.: 300%
P6-13
Reverse
Regenerative
Torque Limit
Default: 200%
Min.: 0%
Max.: 300%
P6-14
Torque Limit
Integral Time
Constant
Sets the integral time constant for the torque
limit. Set shorter time for faster torque limit
Default: 200 ms
Min.: 5 ms
Max.: 10000 ms
P6-15
Torque Limit
Control Selection
during Acc./Dec
0 : Proportional Control (Integral Control at
constant speed)
1 : Integral Control
Default: 0
Range: 0, 1
P7: Controller Protection
P7-00 Input Phase Loss
Protection
Enables or disables the input phase loss
detection.
0
∶
Disabled
1
∶
Enabled
Default: 1
Range: 0, 1
P7-01 Output Phase Loss
Protection
Sets the output phase loss detection.
0 : Disabled
1 : Enabled when One Phase is Lost
2 : Enabled when Two Phases are Lost
Default: 0
Range: 0, 1, 2
P7-02 Output Ground
Fault Detection
Enables or disables the output ground fault
detection.
0
∶
Disabled
1
∶
Enabled
Default: 0
Range: 0, 1
P7-03 Heatsink Cooling
Fan Operation <6>
Sets the heatsink cooling fan operation.
0 : Enabled when controller is running
1 : Enabled when power supply is On
2 :
When the fin temperature reaches 60
degrees, the fan starts running
Default: 0
Range: 0, 1
P7-04 Heatsink Cooling
Fan Off-Delay Time
When P7-04=0, sets the cooling fan off-delay
time that the controller waits to disabled the
cooling fan after run command is released.
Default: 60 s
Min.: 0 s
Max.: 300 s
P7-05 Ambient
Sets the ambient temperature.
Default: 40 °C