Parameter
Name
Description
Setting Range
exceeds the value set in P3-01. Acceleration
continues when the output current drops 15%
below the value set in P3-01.
P3-01
Stall Prevention
Level during
Acceleration
Sets the output current level to activate the Stall
Prevention function during acceleration.
Default: Determined
by A1-06
Min.: 0%
Max.: 150%
P3-02
Stall Prevention
Limit during
Acceleration
Sets the lower limit of Stall Prevention in the
constant power range as a percentage of the
controller rated output current.
Default: 50%
Min.: 0 %
Max.: 100 %
P3-03
Stall Prevention
during
Deceleration
0 : Disabled
The controller decelerates according to the set
deceleration time
1 : Enabled (Without Braking Resistor)
Default: 1
Range: 0, 1
P3-04
Stall Prevention
Level during
Deceleration
Sets the voltage level to activate the Stall
Prevention function during deceleration.
Default: <8>
Min.: 330V
Max.: 410V <3>
P3-05 Stall Prevention
during Run
0 : Disabled
1 : Enabled (Deceleration Time 1)
2 : Enabled (Deceleration Time 2)
Default: 1
Range: 0, 1, 2
P3-06 Stall Prevention
Level during Run
Sets the current level to activate the Stall
Prevention function during run.
Default: Determined
by A1-06
Min.: 30%
Max.: 150%
P3-11
Stall Deceleration
Time during
Acceleration
Sets the deceleration time for a stall during
acceleration
Default: 0.0 s
Min.: 0.0 s
Max.: 6000 s
P4: Frequency Detection
P4-00 Frequency
Detection Level
Sets the detection level and width for the
multi-function output terminal.
Default: 30.0 Hz
Min.: 0.0 Hz
Max.: Determined by
d1-02, L2-00
P4-01 Frequency
Detection Width
Default: 2.0 Hz
Min.: 0.1 Hz
Max.: 25.5 Hz
P4-02
Frequency
Command Loss
Detection
Selection
Sets the controller operation when a frequency
command loss is detected.
0: Controller Stop
1: Continue operation according to the setting
in P4-03.
Default: 0
Range: 0, 1
Содержание CPSPI3700EVF380