![CWSI CP-3000 Скачать руководство пользователя страница 8](http://html.mh-extra.com/html/cwsi/cp-3000/cp-3000_operating-and-installation-instruction-manual_2701246008.webp)
8
Section 2 – Specifications and Compatibility
2.1 Specifications
Power Source: 120 VAC 60Hz 4 Amp dedicated circuit.
Batteries: Two 12Vdc 7Ah sealed lead acid batteries connected in series for up to 60 hours standby
operation.
Operating Temperature: 32 to 120 degrees F.
Operating Humidity: 85% non-condensing
Special Application NAC Circuits: Programmable Power Limited. 1 Class “A” (Style Z) or 2 Class “B”
(Style Y) Field selectable.
Class A ratings: 12 or 24 Volts DC @ 2 Amps each
Class B ratings: 12 Volts DC @ 2 Amps each or 24 Volts DC @ 1 Amp each
Dry Contact Alarm Relays:
4 N.O. non-programmable power limited rated 28 Vdc @ 1 Amp. resistive.
2 Form “C” programmable power limited rated 28 Vdc @ 1 Amp. resistive.
Dry Contact Trouble Relays:
2 N.O. non-programmable power limited rated 28 Vdc @ 1 Amp. resistive.
2 N.C. non-programmable power limited rated 28 Vdc @ 1 Amp. resistive.
Auxiliary output: Current 300 ma. Max coil resistance 14.6 ohms.
Data Port: RS-232 – 9 Pin Computer connector.
Ethernet port connector: RJ-45
Telco input: RJ-11
Transceiver Operating Frequency: 900 MHz band.
Antenna Types: Yagi and Folded Dipole Omni. Max Coax length 20 ft.
Transmission Format: Frequency Hopping – Spread Spectrum.
Dimensions: 17” high, 17” wide, 3 ¼” deep
Enclosure: Powder coated 16 gauge steel