Buttons and functions are:
Alarm Ack
Pressing this button during an alarm will silence the internal piezo sounder and change the Fire LED
from flashing to steady. The piezo will beep once every 30 seconds until the system is reset to
normal. If a different device goes into alarm, the piezo will resound an alarm. More than 5
simultaneous alarms will cause the screen to scroll through the displayed alarms at 5 second
intervals. Pressing the Alarm Ack button a second time will cease this rotation. The alarm display can
then be rotated using the soft key arrow buttons Previous or Next.
Supervisory Ack
Pressing this button during a supervisory will silence the internal piezo sounder and change the
Supervisory LED from flashing to steady. The piezo will beep once a minute until the system is reset
to normal. If a different device transmits a supervisory condition, the piezo will resound the
supervisory tone. More than 5 simultaneous supervisory conditions will cause the screen to scroll
through them at 5 second intervals. Pressing the Supervisory Ack button a second time will cease this
rotation. The display can then be rotated using the soft key arrow buttons Previous or Next.
Trouble Ack
Pressing this button during a trouble will silence the internal piezo sounder and change the Trouble
LED from flashing to steady. The piezo will beep once every 2 minutes until the system is reset to
normal. If the panel is not reset to normal within 4 hours or a different device transmits a trouble
condition, the piezo will resound the trouble tone. More than 5 simultaneous trouble conditions will
cause the screen to scroll through them at 5 second intervals. Pressing the Trouble Ack button a
second time will cease this rotation. The display can then be rotated using the soft key arrow buttons
Previous or Next.
Signal Silence
This button performs the same functions as the Alarm Ack button except it will also reset any active
NAC circuits, Alarm dry contact relays and Auxiliary output. The Signals Silenced LED will also turn
on if NAC circuits are silenced. Resetting the system to normal will turn off the Signals Silenced LED.
Reset
Pressing this button will reset the system to normal. All active LED’s, NAC circuits, Dry contact relays,
Auxiliary output, LCD display and piezo will be restored to normal standby condition. If the system
was in test mode, it will be returned to normal standby. If any Alarm, Supervisory or Trouble that
exists after reset will cause the system to once again annunciate that condition.
Panel Test
Pressing this button will activate the Test LED and display a test menu on the LCD allowing the user
to choose the particular test desired. Refer to system testing for additional information. Pressing reset
will return the system to normal standby.
Horns On
This button will activate any programmed NAC circuits. It may also activate other relays if
programmed to do so. Refer to programming section for options. The piezo will also sound for an
alarm if the button is pushed when no alarm is present on the system.
Enter
Used for system programming. Refer to programming section.