3.5.4 Auxiliary Output Local Energy Municipal Box Service (TB3 Terminals 1+2)
This is a programmable output for connection to a city municipal box using series connection only.
Shunt connection is not supported. This output is supervised and can be programmed to activate
when any one of the 4 alarm types A, B, C or D are in process. A jumper labeled JP1 located on the
CP-3000 motherboard can be used to temporarily disable the auxiliary output. This is useful when
tripping of the municipal box is not desired while performing system testing in normal mode. Placing
the jumper on pins 2+3 will disable the output. This will cause a system trouble to be displayed.
Removing the jumper completely or placing it on pins 1+2 will enable the output. Note: The auxiliary
output must first be programmed to activate before the auxiliary output and jumper JP1 will function.
There are also reset options available when this feature is used. Refer to the programming section for
further instructions. Alarm C must not be programmed to activate the auxiliary output when it is
designated as sprinkler supervisory. No termination resistor is needed when this output is not
programmed to activate.
Output Ratings:
Alarm current 250ma.
Alarm voltage 3.625 Volts D.C.
Coil resistance 14.5 ohms
Max. coil resistance 14.6 ohms
Max. wire resistance 3 ohms