25
9. Power Loss – Can occur in AR-3 repeater or CP-3000 control panel. Caused by low or no
voltage present at A/C input to product. Trouble relay activation will be delayed by 90 minutes.
10. Maintenance Required – Can occur in model 300 smoke detector. Caused by sensitivity level
error or hardware failure in the smoke detector head.
4.2.5 System Test
A full system test of all initiating devices can be performed as required by NFPA or local authorities.
During testing the programmed NAC circuits can be silent or activate for 5 seconds when an alarm is
sent from a device. Transmitter signals received while in test mode are stored in a special test log
allowing for an annual testing printout to be generated by downloading the information via the RS-232
port connected to a computer. Test log memory has a capacity of 1000 signals. The trouble relay will
activate while the CP-3000 is in test mode. Test mode is entered by pressing the system test button
and then entering the 4 digit pass code.
4.2.6 Memory Recall
The CP-3000 has the capability of storing 1000 alarms, 1000 supervisory/trouble 1000 test and 150
keypad button presses. This information can be downloaded and printed separately or in various
groupings. These memory lists can also be individually cleared which requires a password.
Section 5 - Digital Alarm Communicators
All communicators will be connected via on board normally open dry contact outputs.
If off premises communications are required, the following DACT’S may be used for connection to the
CP-3000 control panel. Wiring diagrams are also included to show proper connections.
This section to be completed before product is submitted. At least 2 dialers will be used.
Section 6 - System Programming
This section details system programming options not previously explained. This includes repeater
relay activation and deactivation (NAC circuits), delays, etc. This section will be completed prior to
submitting product. Some options will include total EVAC, EVAC by zone, relay repeater activation,
etc.