background image

26

I.B. 8926-1A

CONTACT WEAR AND REPLACEMENT

Contactors are subject to both mechanical and
electrical wear during their operation. In most cases
mechanical wear is insignificant. The erosion of the
contacts is due to electrical wear. During arcing,
material from each contact is vaporized and blown
away from the useful contacting surface.

A critical examination of the appearance of the
contact surfaces and a measurement of the
remaining contact over-travel will give the user the
information required to get the maximum contact life.

OVER-TRAVEL MEASUREMENT

Contact life has ended when the over-travel of the
contacts has been reduced to .020 inch.

Over-travel of the contact assembly is that part of
the stroke which the moving contacts would travel
after touching the fixed contacts if they were not
blocked from movement by the fixed contacts.

A method of measuring over-travel is as follows:

A. Place a .020 inch feeler gauge between the

armature and magnet, with the armature held
tightly against the magnet.

B. Check continually in each phase, i.e.,

determine if circuit from terminal-to-terminal for
each pole is open under these conditions.

C. If there is continuity through all phases, the

remaining over-travel is sufficient. If there is not
continuity through all phases, replace all
stationary and moving contacts plus moving
contact over-travel springs. After replacing
parts, manually operate  contactor to be sure
binding does not occur.

DEFECT

CAUSE

REMEDY

Short contact 
life

Low contact 
force

Adjust overtravel, replace 
contacts, and replace contact 
springs as required to correct 
contact force.

Contact bounce 
on opening or 
closing

Correct improper voltage 
applied to coil. Correct any 
mechanical defects or 
misalignment.

Abrasive dust 
on contacts

Do not use emery cloth to 
dress contacts.

Load current is 
too high

Reduce load. Use larger 
contactor.

Jogging cycle 
is too severe

Reduce jogging cycle. Check 
factory for more durable 
contact material. Use larger 
contactor.

CONTACTOR TROUBLESHOOTING CHART

DEFECT

CAUSE

REMEDY

Overheating

Load current 
too high

Reduce load. Use larger 
contactor.

Loose 
connections

Clean discolored or dirty 
connections and retighten. 
Replace poorly crimped lugs.

Over-travel 
and/or contact 
force too low

Adjust over-travel, replace 
contacts, and replace contact 
springs as required to correct 
defect.

Ambient 
temperature 
is too high

Reduce load. Provide better 
ventilation. Relocate starter. 
Use larger contactor.

Line and/or 
load cables 
are too small

Install terminal block and 
run larger conductors 
between contactor and 
terminal block.

CONTACTOR TROUBLESHOOTING CHART

Welding of 
contacts

Overtravel 
and/or contact 
force is too low

Adjust overtravel, replace 
contacts, and replace contact 
springs as required to correct 
contact force.

Magnet 
armature stalls 
or hesitates at 
contact touch 
point

Correct low voltage at coil 
terminals as coil draws inrush 
current.

Contactor 
drops open to 
contact-touch 
position 
because of 
voltage dip

Maintain voltage at coil 
terminals. Install low voltage 
protective device, sometimes 
called "Brownout Protector".

Excessive 
contact bounce 
on closing

Correct coil overvoltage 
condition.

MAINTENANCE OF MOTOR CONTROLLERS
AFTER A FAULT

=

In a motor branch circuit which has been properly
installed, coordinated and in service prior to the
fault, opening of the branch-circuit short-circuit
protective device (fuse, circuit breaker, motor short-
circuit protector, etc.) indicates a fault condition in
excess of operating overload. This fault condition
must be corrected and the necessary repair or

Содержание Freedom 2100 Series

Страница 1: ...Views 31 12 Related Instruction Leaflets 33 This electrical control equipment is designed to be installed operated and maintained by adequately trained workmen These instructions do not cover all det...

Страница 2: ...10 which can be removed for installation and maintenance operations Adequate space is provided for control wiring and top cable entry At the bottom of each section a door 18 provides ready access to...

Страница 3: ...on each handle The device panel 5 is mounted on the drawout unit It will accommodate up to six pilot devices The overload reset button 20 is mounted on the unit door 1 Unit Door 2 Drawout Unit 4 Turn...

Страница 4: ...and after unloading the motor control center inspect each section and unit exterior for evidence of damage that may have been incurred during shipment If there is any indication that the control cent...

Страница 5: ...rdance with both the National Electrical code NEC NFPA 70 and the National Electrical Safety Code NESC ANSI C2 Caution If work is involved in connecting the control center with existing equipment ensu...

Страница 6: ...nd wire having a size in accordance with NEC 250 94 from the grounding electrode to the MCC ground bus or ground terminal provided See also NEC 250 91 a and 92 b ii If the system is grounded at any po...

Страница 7: ...amp the rear upright channels together In front mounted only structures this will require removal of the adjacent back sheets In a back to back mounted structure remove the vertical wireway doors and...

Страница 8: ...hrough 10 represents the backside of the MCC The top portion of each of these figures applies to 20 deep enclosures and the lower portion to 16 deep enclosures Note that for all but the single bar per...

Страница 9: ...TROL Consult the assembly instruction supplied with every Freedom 2100 Motor Control Center set up for splice to Freedom Unitrol or F10 Unitrol Fig 11 Splice Plates Attached to Freedom 2100 Horizontal...

Страница 10: ...oad be sure to have each conduit carry conductors from each phase and the same number of conductors per phase If the phase conductors are not distributed uniformly eddy currents will be generated in t...

Страница 11: ...be wired outside of the vertical wireway To engage the terminal block align the fingers of the male connector with the slot at the back of the female portion of the terminal block Then rotate the mal...

Страница 12: ...C and the 10 foot rule and the 25 foot rule of NEC 240 21 apply These latter exceptions to the general rule allow the disconnect means and Fig 17 Main Disconnect with Stab Load Connections overcurrent...

Страница 13: ...metrical the installing electrician needs to anchor the cables at the incoming line connections sufficiently and tighten the lugs correctly Each incoming line compartment is equipped with a two piece...

Страница 14: ...applications such as jogging Class 10 or 20 heater packs Fig 24 Use Class 10 heaters with fusible or thermal magnetic breaker disconnects only Bimetallic ambient compensated operated Trip free mechan...

Страница 15: ...trip setting which does not exceed the calculated figure of Item 2 This is the maximum setting that should be used 4 Depress and turn the screwdriver adjustment counter clockwise one setting at a tim...

Страница 16: ...used select the wire size as if the conductors had an insulation temperature rating of 75 C even if the conductors actually used have a temperature rating higher than 75 C Protect heater and starter a...

Страница 17: ...TIC RESET The overload relay is factory set at M for manual reset operation as shown in the illustration For automatic reset operation turn the reset adjustment dial to the A position Automatic reset...

Страница 18: ...MPERES 3 90 N 14 4 135 MAXIMUM RATINGS Minimum Wire Size 6 AWG l NOTES Part Winding Starters Select heater packs for 50 of the motor FLA Wye Delta Starters Select heater packs for 58 motor FLA u For m...

Страница 19: ...shed 11 Set any adjustable current and voltage trip mechanisms to the proper values 12 Ensure that overload relay heater elements are installed and selected to the full load current shown on the namep...

Страница 20: ...emoving the unit door the control unit is exposed With a screwdriver push in on the latch at the top center of the unit and rotate turn counterclockwise CAUTION Units 18 or more high have a retaining...

Страница 21: ...is withdrawn free of the linkage a spring automatically moves the shutter to its closed position See Figure 31 and Figure 4 With the control unit removed the shutter should completely cover the stab...

Страница 22: ...1 Remove the existing blank door 2 Position the new unit door over the open space to ensure the hinges and latches are aligned If the spaces differ the hinges and latches on the structure must be re l...

Страница 23: ...g and adjusting the electrical equipment refer to the applicable drawings covering the specific motor control center MCC and any other related interconnection drawings Follow any instructions which ma...

Страница 24: ...nts charred insulation discolored terminals etc Mechanically clean to a bright finish don t use emery paper or replace those terminations that have become discolored Determine the cause of the loose j...

Страница 25: ...racket does not need field adjustment The interlock bracket will be adjusted to almost touch the side of the unit interlock rod when the operator is in the on position Fig 35 6 Inch Breaker Unit Slide...

Страница 26: ...d to coil Correct any mechanical defects or misalignment Abrasive dust on contacts Do not use emery cloth to dress contacts Load current is too high Reduce load Use larger contactor Jogging cycle is t...

Страница 27: ...er opening indicates deterioration beyond normal wear and tear such as overheating contact blade or jaw pitting insulation breakage or charring the switch must be replaced Fuse holders Deterioration o...

Страница 28: ...ore quickly than the other three corners This wear is normally due to misalignment of the moving and stationary contacts Contacts should be replaced if it is apparent that one contact is nearly making...

Страница 29: ...9 2756 13 9 1891 20 9 1891 20 380 415V 50 Hz L 9 2703 8 9 2703 8 380V 50 Hz L 9 2756 12 9 1891 14 9 1891 14 415V 50 Hz M 9 2756 8 9 1891 21 9 1891 21 550V 50 Hz N 9 2756 14 9 1891 8 9 1891 8 C306KN3 C...

Страница 30: ...t Guides Included with Item 3 5 Quarter Turn Latch Included in Item 9 4 Freedom Starter 3 Unit Frame 2 Heater Mounts 1 8 Stab Assembly 9 Unit Drawout Handle 10 Unit Terminal Blocks 11 Control Power Tr...

Страница 31: ...31 I B 8926 1A Part 11 PLAN VIEWS...

Страница 32: ...e removed to provide maximum unrestricted conduit space at the bottom of the MCC 5 This conduit space is not recommended when a neutral bus is required Otherwise available See side View A far right fo...

Страница 33: ...t height above floor line is 3 50 inches 3 Maximum conduit space with channel sills is 17 50 X 9 73 inches 4 For multiple structure assemblies either one or both of these members are removed to provid...

Страница 34: ...g and Reversing vacuum I L 16999 Size 5 Non Reversing and Reversing vacuum I L 17088 Circuit Breakers Series C F frame I L 29C101 Series C J frame I L 29C103 Series C K frame I L 29C104 Series C L fra...

Отзывы: