Chapter 2: Pre-Installation Planning
WARNING
The maximum distance of the DC power cable is 500ft (150m) with a wire of 16AWG
from the EDGE Expansion Box to the last EDGE 2 Controller on the EDGE network.
Over this distance, use an EDGE PSU 24V 36W to supply power to the EDGE 2
Controllers. In this case, do not use the 24Vdc from the EDGE Expansion Box.
Figure 2-1
Distance > max. distance with 16 AWG — no redundant power
EDGE 2 Controller Screenless
The EDGE 2 Controller Screenless can be used only as a Redundant Main Controller in a redundancy
system scheme.
NOTE:
Use only Ethernet cables with EDGE 2 Controller Screenless for Ethernet network. The router
must have DHCP function when using this type of controller.
EDGE 2 Remote Display
Use the EDGE PSU 24V 36W to power the EDGE 2 Remote Display. This will make sure the EDGE
Expansion Box power supply is not overcharged.
The EDGE 2 Remote Display needs an EDGE 2 Main Controller to control the EDGE system indirectly.
An EDGE network without a Main Controller is impossible.
26
890–00687
EDGE 2
Содержание 064-11343
Страница 7: ...Chapter 1 Introduction Figure 1 2 Enclosure Identification 890 00687 EDGE 2 7...
Страница 22: ...NOTES 22 890 00687 EDGE 2...
Страница 30: ...Chapter 2 Pre Installation Planning 30 890 00687 EDGE 2...
Страница 40: ...NOTES 40 890 00687 EDGE 2...
Страница 58: ...NOTES 58 890 00687 EDGE 2...
Страница 98: ...NOTES 98 890 00687 EDGE 2...
Страница 112: ...NOTES 112 890 00687 EDGE 2...
Страница 116: ...NOTES 116 890 00687 EDGE 2...
Страница 120: ...NOTES 120 890 00687 EDGE 2...
Страница 134: ...NOTES 134 890 00687 EDGE 2...
Страница 135: ...F Extending a cable Best practice using a junction box 890 00687 EDGE 2 135...
Страница 136: ...Appendix F Extending a cable Using of heat shrink tubing 136 890 00687 EDGE 2...