Appendix C: Technical Specifications
Allowable loss of performance in a noisy environment:
Accuracy of ±80mV from initial reading with a voltage source of 1% precision used for test-
ing purpose.
Analog 4-20mA
Sensor must be able to drive a 120 Ohms load
Maximum rating: 20.8mA, 2.5V
Accuracy of ±0.2mA in a normal operation.
Allowable loss of performance in a noisy environment:
Accuracy of ±0.4mA from initial reading with a current source of 1% precision used for test-
ing purpose.
Dry contact
Close contact resistance must be lower than 200 Ohms
Open contact resistance must be higher than 100k Ohms
Water meter, Pulse
speed
Max 100Hz, pulse width minimum of 3.2ms
Max 100 Ohms (close contact) and min. 100k Ohms (open contact) including the value of
the wire resistance
Variable output
module (SSR) cur-
rent sensor
Frequencies range : 40-70 Hz.
Accuracy of ±0.6A for AC load <20A in a normal environment.
Allowable loss of performance in a noisy environment:
Accuracy of ±0.8A from initial reading with a load of 1% precision used for testing purpose
Relay outputs with
current sensing
input
Accuracy of ±0.5A for AC load <20A in a normal environment.
Allowable loss of performance in a noisy environment:
Accuracy of ±0.75A from initial reading with a load of 1% precision used for testing
purpose
Current sensing
input
Accuracy of ±0.5A for AC load <20A in a normal environment
Allowable loss of performance in a noisy environment:
Accuracy of ±0.75A from initial reading with a load of 1% precision used for testing
purpose
Auxiliary outputs
0-10 VDC outputs
0-10VDC, accuracy : 1% (means, 0.1V), output impedance : 50 Ohms, Max current per
output : 20mA for each output
0-10Vdc outputs on
EDGE 4IN-2V-8DO
0-10Vdc, accuracy : 1% (means, 0.1V), output impedance : 50 Ohms, Max current per
output : 100mA
24 VDC outputs
24 VDC, 50 mA for each output
Operational specifications
Operating
Temperature
0 to 40°C (32 to 104°F)
Storage
Temperature
-20 to 50°C (-4 to 122°F)
890–00687
EDGE 2
127
Содержание 064-11343
Страница 7: ...Chapter 1 Introduction Figure 1 2 Enclosure Identification 890 00687 EDGE 2 7...
Страница 22: ...NOTES 22 890 00687 EDGE 2...
Страница 30: ...Chapter 2 Pre Installation Planning 30 890 00687 EDGE 2...
Страница 40: ...NOTES 40 890 00687 EDGE 2...
Страница 58: ...NOTES 58 890 00687 EDGE 2...
Страница 98: ...NOTES 98 890 00687 EDGE 2...
Страница 112: ...NOTES 112 890 00687 EDGE 2...
Страница 116: ...NOTES 116 890 00687 EDGE 2...
Страница 120: ...NOTES 120 890 00687 EDGE 2...
Страница 134: ...NOTES 134 890 00687 EDGE 2...
Страница 135: ...F Extending a cable Best practice using a junction box 890 00687 EDGE 2 135...
Страница 136: ...Appendix F Extending a cable Using of heat shrink tubing 136 890 00687 EDGE 2...