48
Start Up
Cycle test
Firing
Safety unit settings and checks
Safety unit settings and checks
Gas pressure switch.
·
Remove the cover to gain access to
the adjust screw.
·
Connect a pressure gauge to
pressure take-off
119 upstream
.
·
Read the actual supply pressure.
·
Switch the burner on.
·
Slowly close the shut-off valve.
Once the theoretical minimum pressure
(see table) is reached:
·
Determine the cut-off point by
turning screw
E
clockwise (
+
).
The burner should stop due to
insufficient gas pressure.
·
Turn the screw anticlockwise (
–
) one
turn (corresponds to 15 to 25daPa).
·
Check the setting by repeating the
test. Pressure switch is set.
m
Air pressure switch
·
Remove the terminal cover.
·
Connect a pressure gauge to the
+
pressure take-off.
·
Reopen the shut-off valve.
When the burner has been refired,
slowly turn screw
V
clockwise
(+
).
Determine and measure the cut-off
point (safety lockout).
·
Turner screw
V
anticlockwise (
–
)
one turn to set the required value
(differential 10-20daPa).
·
Restart the burner.
·
Gradually close off the burner air
intake.
·
Check that the CO value remains
below 1000ppm prior to safety
lockout.
If not, increase the air pressure switch
setting and restart the test.
·
Disconnect the gas measurement
instruments.
·
Reclose the pressure take-offs.
·
Restart the burner.
·
Check for leaks downstream from
the valve assembly and between
flange and burner front.
·
Simultaneously disconnect both
microammeter cables.
The burner should immediately lock out
to safety.
·
Put the ionization bridge back in its
place.
·
Put the covers back in their places.
·
Restart the burner.
·
Check the combustion parameters
under actual service conditions
(doors closed, etc.) and test the
various connections for gas leaks.
·
Record the results in the relevant
documents.
·
Set the burner to automatic mode.
·
Convey the information required for
operation to those concerned.
Burner
power
(kW)
Burner head gas pressure
G20 G25
G31
Air flap
position
103 B
0 to 18
Burner head
air pressure
pL
(daPa)
Dimension
Y
(mm)
119 pBr
(daPa)
(daPa)
NC4
15
25
35
11
24
37
6
15
27
3,5
8
12
8
18
22
17
20
25
NC6
40
50
47
63
40
45
13
18
27
29
25
30
NC9
60
70
85
50
64
97
66
84
120
9
11
18
35
36
52
25
30
35
Cycle test
·
Open and immediately reclose the
shut-off valve.
·
Switch the burner on.
·
Close the regulation circuit.
·
Unlock the control and safety unit
and check that it is working
correctly.
The program sequence should be as
follows:
–
controlled preventilation time
20 sec. (total preventilation time can
exceed 20 sec.),
–
electrode ignition 3 seconds,
–
the valves open,
–
the valves close no more than
3 seconds after opening,
–
burner stops due to either lack of
gas pressure or control and safety
unit lockout due to flame
disappearance.
If unsure, repeat above test.
Firing is only possible after this
essential test of the ignition cycle has
been carried out.
Firing
Warning:
The unit may be fired when all the
requirements listed in the previous
sections have been met.
·
Connect a microammeter scale
0-100µA DC in place of the
ionization bridge
B1
(check polarity).
·
Open the shut-off valve.
·
Close the thermostat circuit.
·
Unlock the control and safety unit.
The burner will operate.
·
Perform a combustion test (CO - CO
2
),
as soon as the flame appears.
·
Check the ionization current (value
between 8 and 20µA).
·
Measure and compare (table):
– gas flow at the meter,
– gas pressure at point
pBr
and at
point
119 upstream
,
– air pressure at point
pL
.
·
If necessary, adjust:
– gas pressure using screw
D
for
NC4/6 and screw
PG
for NC9
– air pressure using setting knob
103B
– dimension
Y
with screw
15
.
·
Check combustion parameters.
The manufacturer’s recommandations
concerning: flue gas temperatures
(boiler) and CO
2
(burner) should be
followed in order to obtain the required
level of performance.
·
With the burner working, and using
a foam designed for this purpose,
check for leaks in the valve
assembly connections.
No leaks should be observed.
Should analysis of the combustion tests
reveal that the CO value is too high,
modify it using the following diagrams:
1
Standard,
2
Modified
·
Fit the two crosspieces
C
(stored on
the plate) between turbulator
A
and
diffusor
D
.
Содержание 13 009 306
Страница 14: ...01 2005 Art Nr 13 010 553B 14 ...
Страница 52: ...01 2005 Art Nr 13 010 553B 52 ...
Страница 58: ...01 2005 Art Nr 13 010 553B 58 ...
Страница 59: ...59 01 2005 Art Nr 13 010 553B ...