10
CTC EcoAir 610M / 614M / 622M 400 V 3N~
EcoAir 610M
53/53 dB(A)
34/34 dB(A)
28/28 dB(A)
EcoAir 614M
51/52 dB(A)
32/33 dB(A)
26/27 dB(A)
EcoAir 622M
55/55 dB(A)
36/36 dB(A)
30/30 dB(A)
EcoAir 610M
EcoAir 614M
EcoAir 622M
588402001
588400001
588401001
400 V 3N~ 50Hz
400 V 3N~ 50Hz
400 V 3N~ 50Hz
kW
0.54 / 2.20
0.54 / 3.94
0.94 / 6.03
kW
2.55 / 6.20
2.55 / 8.69
4.75 / 13.99
COP
1)
4.71 / 2.82
4.71 / 2.21
5.07 / 2.32
A
7.1
10.2
16.9
A
6.6
9.4
15.5
A
2.7
2.7
4.9
Ω
-
-
0.12
liter
1.9
1.9
2.8
kg
2.2
2.2
2.7
ton
3.903
3.903
4.790
°C
65/15
65/15
65/15
MPa (bar)
0.25/0.05 (2,5/0,5)
0.25/0.05 (2,5/0,5)
0.25/0.05 (2,5/0,5)
MPa (bar)
3.1 (31)
3.1 (31)
3.1 (31)
°C
100/0
100/0
100/0
MPa (bar)
0.3/0 (3.0/0)
0.3/0 (3.0/0)
0.3/0 (3.0/0)
mm
545 x 1245 x 1080
545 x 1245 x 1080
610 x 1375 x 1180
Inverter scroll /
PVE FV50S
Inverter scroll /
PVE FV50S
Inverter scroll /
PVE FV50S
m
3
/h
3129
3129
5457
rpm
W
54
54
148
kg
174 (204)
174 (204)
192 (226)
dB (A)
53/53
51/52
55/55
dB (A)
53
53
53
IP X4
IP X4
IP X4
Heat pump Certificate No.
012-SC0516-18
012-SC0319-18
012-SC0320-18
CTC no.:
Electrical data
Input power
1)
Output power
1)
Rated current
2)
Rated current with temp. limit.
Max start current
Maximum permitted impedance at connection*
Water volume
Refrigerant quantity R407C, fluorinated
greenhouse gases GWP 1774
)
CO
2
equivalent
Max/min system temperature
Max/min system pressure
High pressure switch HT
Max/min temp. (TS) (PED)
Max/min pressure (PS) (PED)
Dimensions
(Depth x Width x Height)
Compressor / Oil type
Air flow 100%
Fan speed
Modulating
Fan, max power
Weight (packaged weight)
Sound power in accord. w. ecodesign
3)
Sound power Silent Mode
4)
Ingress Protection (IP)
1)
At 35°C water temperature. +7 @ min rps / -7 °C @ max rps. According to EN 14511.
2)
At max rps incl. Grundfos UPM GEO 25-85 charge pump.
3)
Sound power level in accordance with EN12102 appendix A.4 i at test conditions A7 W47/55 and A7 W30/35.
*Maximum permitted impedance at the mains connection according to EN 61000-3-12. If the impedance at the mains connection is higher than
the specifi ed, check with the grid owner before purchasing the equipment.
4)
Silent Mode requires software version 191128 or higher and is available in combination with CTC EcoLogic (software version 191203 or
higher). Active silent mode reduces heating performance and effi ciency.
No annual leakage control of the refrigerant is required.
Sound power
Sound pressure 5 m
Sound pressure 10 m
!
Note: In case of deviations, the product's data plate applies. When servicing always check
the product's data plate for correct refrigerant quantity.
Noise data
The stated sound values should be considered an indication only, as the level is affected both by power output and the surroundings
3. Technical data
Содержание 588400001
Страница 2: ......
Страница 32: ...32 CTC EcoAir 610M 614M 622M 400 V 3N 6 9 Wiring diagram 400 V 3N A3...
Страница 33: ...33 CTC EcoAir 610M 614M 622M 400 V 3N...
Страница 34: ...34 CTC EcoAir 610M 614M 622M 400 V 3N 6 10 Wiring diagram 400 V 3N A4...
Страница 40: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 012 162 505 89 1 2020 09 14...