6.2.4.3
110V Voltage Transformer (VT) Circuits or 400V/550V Direct (Delta/3-
wire systems)
Always connect the safety earth terminal located on the power
connector first!
Table 12: VT circuit connection layout for 3-wire delta connection
Terminal
Legend
110V VT Circuit or 400V/550V Delta (3-wire) Systems
1.
V
1
Phase 1
2.
V
2
Phase 2
3.
V
3
Phase 3
4.
V
com
Open (Note: V
com
may also be connected to the earthed
Phase/Phase 2 on 110V VT circuits)
5.
V
4+
Open
6.
V
4-
Open
1)
Connect Phase 1,2 and 3 to Voltage Inputs 1-3 as shown in the Figure 60.
2)
Leave V
com
open or connect V
com
to the earthed Phase (Phase 2) on 110V VT
circuits.
Figure 63: Impedo Duo 3-wire delta connection