Table 2: Voltage connection layout
Terminal
Legend
Description
1.
V
1
Phase 1
2.
V
2
Phase 2
3.
V
3
Phase 3
4.
V
com
Reference for V
1-3
5.
V
4+
Phase 4
6.
V
4-
Reference for V
4
A single 600 V
AC-RMS
voltage input range with 20 mV resolution simplifies installation
and ensures good accuracy for both the fundamental component and harmonics.
A high impedance input prevents the accidental shorting of VT inputs to system
ground and eliminates ground loops. Differential resistive inputs assure a safe, stable
analog input stage with minimum phase error, high bandwidth and zero temperature
drift.
2.4.4
Current Sensor Inputs
Each individual meter contains 4 galvanically isolated resistive current shunt inputs
with input impedance of 20 mΩ and a full-scale measurement range of 6 A
RMS
.
Resistive shunts provide excellent AC and DC response; zero offset drift and very low
temperature drift.
The 3-second over current withstand rating of each input is 50 A. The galvanic
isolation voltage between each channel and earth is 1 kV.
The current inputs are available on an 8-terminal lockable connector plug with screw
terminals for meter A and B as shown in Figure 12. Each terminal can accommodate
conductors with size up to 2.5mm
2
.
Содержание Impedo DUO
Страница 28: ...Impedo DUO User Guide 28 Figure 5 Back of instrument Figure 6 Right side of instrument GPS USB 1...
Страница 85: ...Impedo DUO User Guide 85 Figure 49 Export harmonic selection...
Страница 109: ...Impedo DUO User Guide 109 Appendices 8 Impedo DUO dimensions...
Страница 110: ...Impedo DUO User Guide 110 8 1 Panel mounting plates 8 2 19 installation plate...
Страница 111: ...Impedo DUO User Guide 111 9 Impedo DUO wiring diagram...
Страница 113: ...Impedo DUO User Guide 113 11 Portable ImpedoDUO...
Страница 117: ...Impedo DUO User Guide 117 Screw driver USB with meter key Ethernet cable...