background image

Page 3

Digital Interface Board (DIB)

............................................................

          Installation

          Display Menu

          User Settings Menu

                 Level Control Options Menu

                 Time Dosing Options Menu       

                 Telemetry Menu

                 Alarm History Menu

          Auxiliary Inputs

          Flash Codes

          FCC Information

          DIB Flow Chart

Float System Troubleshooting

..........................................................

  

Enclosure Dimensions

........................................................................

Field Wiring Connections

..................................................................

 

Terminal Strip With All Available Options

 

Determining Your RK Model Number

Float System Specifications

..............................................................

Pages 16 - 22

Pages 23 - 24

Page 25

Page 26

Page 27

RK Series

Содержание RK E Series

Страница 1: ...RKSeries Serious Products for Serious Contractors Float Systems Manual...

Страница 2: ...er Float Indication Status Lights Float System Features Pages 9 10 Hand Run Buttons Blown Fuse Indicators Audible Alarm Circuitry Alternation and Lag Delay Special Options Redundant Off Float Auxiliar...

Страница 3: ...u Telemetry Menu Alarm History Menu Auxiliary Inputs Flash Codes FCC Information DIB Flow Chart Float System Troubleshooting EnclosureDimensions Field Wiring Connections Terminal Strip With All Availa...

Страница 4: ...in a NEMA 4X enclosure Through the use of a standard subdoor and raised backpanel the RK Series is able to house common control panel features such as circuit breakers start components contactors and...

Страница 5: ...tank and then install the floats and weights into the cord snubbers Warning 1 Do not install a float switch in direct line of incoming liquid 2 Make sure you leave at least 3 5 inches of tether lengt...

Страница 6: ...using the provided mounting feet 5 Bring the float wires and power wires into the panel through the conduit 6 Wire the panel according to the schematic included in the panel 7 Check installation by tu...

Страница 7: ...s Typical Float System Installation Diagram RK Series Note Care should be taken to ensure that sewage gases are not allowed to enter the control panel by using an approved gas sealing means Damage cau...

Страница 8: ...e automatically cleared next time the floats sequence in the proper order Another example would occur when the Pumps Off float fails to close when it tips up When the Lead Pump On float tips up the Pu...

Страница 9: ...by simply touching the decal on the side of the enclosure Blown Fuse Indicators These lights are located above the fuses on the subdoor If a fuse is blown the indicator above the blown fuse will light...

Страница 10: ...l has the Auxiliary Alarm Contact option then the terminal strip will include the numbers 17 18 This option offers a dry contact that closes during a high level alarm condition then opens when the ala...

Страница 11: ...running Note 1 When there is a fuse blown condition on a RK E Series controller the blown fuse indicator will light and the power light will continue to be dimly lit Blown Fuse Indicator Alarm Light I...

Страница 12: ...ge between menu fields Et Elapsed Time is Pump number 1 or 2 Reads out the total elapsed run time of the corresponding pump Press Set Change button to alternate between hours and minutes seconds CC Cy...

Страница 13: ...Set Change button to enter into this submenu Level Control Options Menu LSS Lead Selection Setting Duplex Panels Only Display will alternate showing LSS and the current value Press Set Change button t...

Страница 14: ...nel is in Override mode This can be silenced It will be cleared after the Disable Timer times out 1 Only Override the Pump Disable Timer without any alarms 2 Only Sound High Level Alarm without any de...

Страница 15: ...eld 1 Time 1 Pump Enable Setting MIN SEC F1t2 Field 1 Time 2 Pump Disable Setting HR MIN HLtd High Level Delay Simplex Panels Only MIN SEC MENU ENTER MENU ENTER MENU ENTER MENU ENTER MENU ENTER MENU E...

Страница 16: ...enu from the display menu push and hold Menu Enter until you see the Level Cntrl Menu appear on the LCD screen When in the Settings Menu press Menu Enter to cycle through the fields to select a submen...

Страница 17: ...time in the current time cycle If the pump s are running then it indicates the time remaining until the pump s shut off If the pump s are off then it indicates time remaining until the pump s may run...

Страница 18: ...YS turns on at the LEAD PUMP input and Pump 1 ALWAYS turns on at the LAG PUMP input Reset Cyc Cnt This is the cycle count that can be viewed in the Display Menu Reset Cycle Counter to zero is pump num...

Страница 19: ...tting for Override This is the amount of time the pump will be enabled to run once the level reaches the override input at which time the system enters Override Time Dosing mode Time shown is in Minut...

Страница 20: ...the High Level float the panel will sound a High Level Alarm to signal that the liquid level is much higher than expected Press Set Change button to change this field Setting Override Override Warnin...

Страница 21: ...and all three share a common Neutral Input Rating 120 Vac 10mA each Flash Codes Each different alarm is annunciated on the LCD screen The audible and alarm light also flash at different rates for each...

Страница 22: ...Reset Cyc Cnt Reset ETM To Change Fields Pump Time On Pump Time Off Pump Ovrrid On Pump Ovrrid Off Alarm Override High Level Delay Number of Fields To Change Fields Most Recent Alarm 2nd Most Recent A...

Страница 23: ...fuse has blown Replace the fuse with a similiar amperage 5 x 20mm fuse If the new fuse also blows check the incoming field wiring Note Extra fuses are located on the back of the subdoor The Float Ind...

Страница 24: ...undant Off option make sure there is a float switch or jumper wire connected to terminals 7 8 The pump s will not run in automatic IF THEN The High Level Alarm is activated If possible open the tank a...

Страница 25: ...Page 25 Enclosure Dimensions RK Series...

Страница 26: ...rm Aux Alarm Contact Sample RKDF230ACB Terminal Strip Note Terminal strips differ between RK models and options Your panel may be missing some of these terminal strip numbers However this example show...

Страница 27: ...ded Subdoor Blown Fuse Status Lights cULus 508 Listed Maximum 2 HP 12 FLA or 3 HP 17 FLA with HD Option 3 Year Limited Warranty Duplex Includes Alternator Lag Pump Delay 12 7 x 10 6 x 7 8 14 6 x 11 9...

Страница 28: ...Technical support 1 800 746 6287 techsupport sjeinc com www csicontrols com PN1062852B 11 20 2019 SJE Inc All Rights Reserved CSI Controls is a trademark of SJE INC...

Отзывы: