Digital Interface Board (DIB)
Time Dosing Options Menu (Continued)
Pump 2 Ovrrid On
- (Pump Enable Time Setting for Override)
See “Pump 1 Ovrrid On” Description
Time shown is in [Minutes:Seconds] (Maximum time setting is 99:59)
Press Set/Change button to change this field.
Pump 2 Ovrrid Off
- (Pump Disable Time Setting for Override)
See “Pump 1 Ovrrid Off” Description
Time shown is in [Hours:Minutes] (Maximum time setting is 99:59)
Press Set/Change button to change this field.
Alarm/Override -
This setting controls 3 functions of Time Dosing:
Override: When the basin level reaches the Override float (High Level
float on simplex, Lag float on duplex), the panel will override the
Off Timer, and run the pump(s) using the override On and Off times.
Override Warning: When an override occurs, the panel will sound an Override
Warning Alarm, to signal that an override event is occurring.
High Level Alarm: When the basin level reaches the High Level float, the
panel will sound a High Level Alarm, to signal that the liquid level is
much higher than expected.
Press Set/Change button to change this field.
Setting
Override
Override Warning High Level Alarm
Override w/ Alarms
ON
ON
ON
Override-No Warning
ON
OFF
ON
Overide-No Alarms
ON
OFF
OFF
Alarm-No Override
OFF
OFF
ON
High Level Delay
- (High Level Time Delay, Simplex Panels Only):
The High Level Alarm will delay according to the set time. If the fluid level is
above the High Level float for this length of time without interruption the
alarm will begin to sound.
Time shown is in [Minutes:Seconds] (Maximum time setting is 99:59)
Press Set/Change button to change this field.
Number of Fields
- (Duplex Panels Only):
The Time Dosing operation can be set up for “One Field” or “Two Fields.”
- When set to “Two Fields” each pump will be able to run as soon as its
corresponding Off Timer is complete. During override the two pumps
may run at the same time.
- When set to “One Field” each pump will only be able to run when the Off
Timer for
both
pumps is complete. The two pumps will never run at the
same time.