![CSI Controls RK E Series Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/csi-controls/rk-e-series/rk-e-series_manual_2692708014.webp)
Page 14
Digital Display Center (DDC)
F1t1
- (Field 1 Time 1 (Pump Enable Time Setting))
Display will alternate showing “F1t1” and the current value. Time shown
is in [Minutes : Seconds] (Maximum time setting is 99:59)
Press Set/Change button to change this field.
F1t2
- (Field 1 Time 2 (Pump Disable Time Setting))
Display will alternate showing “F1t2” and the current value. Time shown
is in [Hours : Minutes] (Maximum time setting is 99:59)
Press Set/Change button to change this field.
ALOr
- (Alarm / Override Function):
Display will alternate showing “ALOr” and the current value.
Press Set/Change button to change this field.
Possible Settings, Simplex:
(What the High Level input will do)
0 = Override the Pump Disable Timer and Alarm with selected
Time Delay (see HLtd setting). A warning will sound and
flash the alarm light to indicate the panel is in Override
mode. This can be silenced. It will be cleared after the
Disable Timer times out.
1 = Only Override the Pump Disable Timer without any alarms.
2 = Only Sound High Level Alarm without any delays.
Possible Settings, Duplex:
(What the Lag (override) input will do)
0 = Override Pump Disable Timer. A warning will sound and
flash the alarm light to indicate the panel is in Override
mode. This can be silenced. It will be cleared after the
Disable timer times out.
1 = Override the Pump Disable Timer. No warning will sound.
2 = Override function is disabled. Lag float input is ignored.
HLtd
- (High Level Time Delay, Simplex Panels Only):
Display will alternate showing “HLtd” and the current value. The High
Level Alarm will delay according to the set time. If the fluid level is
above the High Level input for this length of time without interruption,
the alarm will begin to sound. Time shown is in [Minutes : Seconds]
(Maximum time setting is 99:59)
Press Set/Change button to change this field.
Time Dosing Options Menu
RK Series
™