Float System Troubleshooting
-Push the “Hand” button to see if
the pump(s) will run in manual
operation. If the pump does not
run in manual operation contact a
local certified professional.
-Check to see if any float indicator
lights are flashing. (See-The
Float Indicator Lights pg 7)
-If the panel has the Redundant
Off option make sure there is a
float switch or jumper wire
connected to terminals 7 & 8.
-The pump(s) will not run in
automatic.
IF
THEN
-The High Level Alarm is activated.
-If possible, open the tank and
verify that the liquid level is a the
high level setpoint.
-Ensure all the circuit breakers
are turned on and that they are
not tripped.
-Push and hold the “Hand” button
to run the pump(s) manually. If the
high level alarm continues after
manually running the pump,
contact a local certified
professional.
RK Series
™