Digital Interface Board (DIB)
Installation
To install the DIB, remove the faceplate from above
the control center on the subdoor and insert the
DIB module from the back of the subdoor (be sure
to remove the protective film on the display before
installing). Next, screw in the four corner screws.
With the power off
, attach the ribbon from the DIB
module to the control board. After everything is
installed, turn the power on. It may take up to 10
seconds for the circuit board to complete the program
update. Once the circuit board has completed the
program update, normal operation will begin. Once a
DIB has been installed, the panel will not work if the
DIB is removed.
Note:
RKE boards are not compatible with the DIB.
Installation Screws
Back of DIB Module
Connecting Ribbon
Make sure power is OFF before installing DIB!
Menu Navigation
To advance to the next menu, press the “Menu/Enter” button. To go to the settings
menu from the display menu, push and hold “Menu/Enter” until you see the “Level
Cntrl Menu” appear on the LCD screen. When in the Settings Menu press “Menu/
Enter" to cycle through the fields, to select a submenu, press the “Set/Change”
button.
Editing Fields
To edit the setting currently being displayed on the screen, press the “Set/Change”
button. The value that is now being edited will begin to flash. To change this value,
press the “Set/Change” button. To move to the next edit digit, or to finish editing the
setting, press the “Menu/Enter” button.
Example
To Change Pump Alternation Features: (Duplex Systems Only)
From the Display Menu press and hold the “Menu/Enter” button until “Level Cntrl
Menu” appears on the LCD screen. Next press the “Set/Change” button to enter
into the Level Control submenu. The first field is “Lead Pump Set”. Press the “Set/
Change” button again to change this field. The field being edited will flash. Press the
“Set/Change” button to change the field and press the “Menu/Enter” button to accept
the setting.
Lead Pump Set
Alternate
Menu/Enter
Button
Set/Change
Button
MENU
ENTER
SET
CHANGE
RK Series
™