Digital Interface Board (DIB)
Level Cntrl Menu - (Level Control Options Menu):
Lead Pump Set
(Duplex Panels Only):
Press Set/Change button to change this field.
Possible Settings
:
Alternate
= Alternates which pump turns on at LEAD PUMP
input every time a pump runs.
Pump 1 is Lead = Pump #1 ALWAYS turns on at the LEAD PUMP
input and Pump #2 ALWAYS turns on at the LAG
PUMP input.
Pump 2 is Lead = Pump #2 ALWAYS turns on at the LEAD PUMP
input and Pump #1 ALWAYS turns on at the LAG
PUMP input.
Reset Cyc Cnt #
- This is the cycle count that can be viewed in the
Display Menu (Reset Cycle Counter to zero, # is pump number (1 or 2)
Possible Settings
:
Do Not Reset
= Cycle Counter will not reset
Reset Counter = Cycle Counter will reset to 0
Reset ETM #
- This is the Elapsed time that can be viewed in the Display Menu
(Reset Elapsed Time to zero, # is pump number (1 or 2)
Press Set/Change button to change this field.
Possible Settings
:
Reset Counter = Elapsed Time will reset to 0
Do Not Reset
= Elapsed Time will not reset