FA510 V1.06
16
Modbus
The dew point sensor FA 510 comes with a Modbus RTU Interface.
Before commissioning
of the sensor
the
communication
parameters
Modbus ID, Baudrate, Parity und Stop bit
must be set in order to ensure the communication with the Modbus master.
The adjustment can be
done either with the CS Instruments
PC
service
software
,
DS
400
,
DS
500
and
the
hand-held instrument
PI
500
done
.
Modbus communication default values:
x
Modbus ID : 1
(1 -247)
x
Baudrate:
19200 bps
(1200,2400, 4800, 9600, 19200, 38400 bps)
x
Parity:
even
(none, even, odd)
x
Stoppbit:
1
(1,2)
Supported are following functioncodes:
x
Function code 03:
Read Holding Register
x
Function code 16:
Write multiple Register
Register Mapping measuring values:
Modbus
Register
Modbus
Address
No.of
Byte
Data Type
Description
Defau
lt
Settin
g
Read
Write
Unit /Comment
1001
1000
4
Float
Temperature
R
[°C]
1003
1002
4
Float
Temperature
R
[°F]
1005
1004
4
Float
Relative Humidity
R
[%]
1007
1006
4
Float
Dew Point
R
[°Ctd]
1009
1008
4
Float
Dew Point
R
[°Ftd]
1011
1010
4
Float
Absolute Humidity
R
[g/m³]
1013
1012
4
Float
Absolute Humidity
R
[mg/m³]
1015
1014
4
Float
Humidity Grade
R
[g/kg]
1017
1016
4
Float
Vapor Ratio (Volume)
R
[ppm]
1019
1018
4
Float
Saturation vapor pressure
R
[hPa]
1021
1020
4
Float
Partial Vapor Pressure
R
[hPa]
1023
1022
4
Float
Atmospheric DewPoint
R
[°Ctd]
1025
1024
4
Float
Atmospheric DewPoint
R
[°Ftd]
Remark for DS400 / DS 500 / Handheld devices - Modbus Sensor Datatyp:
„
Data Typ R4-
32“
match with
„Data Type Float“
Modbus