FA510 V1.06 

 

17 

 

Modbus Settings  (2001…2006)

 

Modbus 
Register 

Modbus 
Address 

No.of 

Byte 

Data Type 

Description 

Default 

Setting 

Read Write 

Unit /Comment 

2001 

2000 

UInt16 

Modbus ID 

R/W 

Modbus ID 1…247

 

2002 

2001 

UInt16 

Baudrate 

R/W 

0 = 1200 
1 = 2400 
2 = 4800 
3 = 9600 
4 = 19200 
5 = 38400 

2003 

2002 

UInt16 

Parity 

R/W 

0 = none 
1 = even 
2 = odd 

2004 

2003 

UInt16 

Number of Stopbits 

 

R/W 

0 = 1 Stop Bit 
1 = 2 Stop Bit 

2005 

2004 

UInt16 

Word Order 

0xABCD 

R/W 

0xABCD = Big Endian 
0xCDAB = Middle Endian 

2006 

2005 

UInt16 

Modbus Enabled 

FA510: 1 
FA515: 0 

R/W 

0 = Modbus disabled 
1 = Modbus Enabled 

 

Analog Scaling Settings   (2007…2011)

 

Modbus 
Register 

Modbus 
Address 

No.of 

Byte 

Data Type 

Description 

Default 

Setting 

Read Write 

Unit /Comment 

2007 

2006 

UInt32 

Output Value 

R/W 

0 = 4-20mA disabled 
1 = Temperature [°C] 
2 = Temperature [°F] 
3 = relative Humidity [%] 
4 = DewPoint [°C] 
5 = DewPoint [°F] 
6 = Absolute Humidity [g/m3] 
7 = Absolute Humidity [mg/m3] 
8 = Humidity Grade [g/kg] 
9 = Vapor Ratio [ppm] 
10 = Saturation Vapor Pressur [hPa] 
11 = Partial Vapor Pressure [hPa] 
12 = Atmospheric DewPoint [°C] 
13 = Atmospheric DewPoint [°F] 

2009 

2008 

float 

4mA Scale Low 

-80 

R/W 

 

2011 

2010 

float 

20mA Scale High 

20 

R/W 

 

 
 
Modbus installation, Modbus

 

settings

 and 

further information

 refer to the 

manual

 

CS 

Instruments

 

"

Modbus 

Installation and Operating Instructions

 

FA

 

5xx

 

sensors

"

 

 

Содержание FA 510

Страница 1: ...with 3 wire technology 4 20 mA and RS 485 Modbus output enables a reliable and long term stable monitoring of the dew point in industrial applications such as in compressed air plants refrigerating a...

Страница 2: ...ctions The proper functioning of the FA 510 and safe operation can only be ensured if the regulations and instructions described are strictly observed Intended Use The dew point sensor is intended for...

Страница 3: ...will prevent soiling of the FA 510 x Standing air leads to long measuring times DESCRIPTION The FA 510 dew point sensor enables a reliable and long term stable monitoring of the dew point in industria...

Страница 4: ...von 50 80 Ctd Pressure range 1 50 bar standard Power supply 24V VDC 10 30 VDC Output 4 20 mA 3 wire technology RS 485 Modbus RTU Protection class IP 65 EMV DIN EN 61326 Operating temperature 20 70 C i...

Страница 5: ...in 3 Pin 4 Pin 5 FA 510 Connector plug VB RS485 A VB RS485 B I Current output Connection cable 0554 0104 5 m 0554 0105 10 m brown white blue black grey VB Positive supply voltage 24VDC 10 30 VDC smoot...

Страница 6: ...uick coupling In case of compressed air containing oil and dirt particles a pre filter should be installed in front of the measuring chamber Compressed air flows continuously at 7 bar approx 1 l min e...

Страница 7: ...er x Function code 16 Write multiple Register Register Mapping measuring values Modbus Register Modbus Address No of Byte Data Type Description Defau lt Settin g Read Write Unit Comment 1001 1000 4 Fl...

Страница 8: ...isabled 1 Modbus Enabled Analog Scaling Settings 2007 2011 Modbus Register Modbus Address No of Byte Data Type Description Default Setting Read Write Unit Comment 2007 2006 4 UInt32 Output Value 4 R W...

Страница 9: ...dition to the warranty service necessary repairs adjustments or similar are carried out the warranty services are free of charge but there is a charge for other services such as transport and packing...

Страница 10: ...ove mentioned components comply with requirements of the following EU directives Elektromagnetische Vertr glichkeit Electromagntic compatibility 2014 30 EUG 2014 30 EC RoHS Restriction of certain Haza...

Страница 11: ...tr 15 D 78052 VS Tannheim Tel 49 0 7705 978 99 0 Fax 49 0 7705 978 99 20 Mail info cs instruments com Web http www cs instruments com Gesch ftsstelle Nord Sales Office North Am Oxer 28c D 24955 Harris...

Отзывы: