JP10, JP110 - CH1  Clock  Detection  Filter

- 3-pin jumper that filters out non-data spikes if clock is not 

present.

Non-dot

 position - presence of clock is detected on the first few positive transition of clock from CH1.

Dot

 position - presence of clock is detected after about 1 ms of positive transitions of clock from CH1. 

JP10,110 normal position - Non-dot

.

JP15, JP16, JP17, JP18 - Alarm clock frequency

 3-pin jumper FACTORY SET to provide clock for the time 

out alarm circuitry. 

DO NOT ADJUST THESE! 

Figure 2.3 shows the correct positions.

.

JP25,JP125 - Clock or data presence alarm enable/disable

 3-pin jumper FACTORY SET to enable clock or 

data presence alarm circuitry on CH1. 

Dot position

-enables clock or data presence alarm on CH1.

Non-dot position

-disables clock or data presence alarm on CH1.

JP26,JP126 - Clock or data presence alarm enable/disable

 3-pin jumper FACTORY SET to enable clock or 

data presence alarm circuitry on CH2. 

Dot position

-enables clock or data presence alarm on CH2.

Non-dot position

-disables clock or data presence alarm on CH2.

2.4.2  On-Card Switches 
S3, S103 - Initial Channel Select (ICS) Mode

- 4-position DIP switch Selects the Initial Channel Select mode 

when JP1,2,3, JP101,102,103,in Dot and JP4, JP104 in Non-dot.

S3, S103 positions 1,2,3,4 to ON - ICS is enabled.

 In the ICS mode, the initial channel can be either 

CH1 or CH2 by switching the front panel Manual Select switch to either CH1 or CH2 and then back to 
the Auto position.or by grounding either Remote 1 or Remote 2 pins on J8 and then grounding the 
Remote reset pin on J8 causing the 1582-14 to go back to Auto in the channel last selected remotely if 
both channel alarms are clear or both channels are in alarm. The initial channel can also be selected if 
both channel alarms are clear or both channels are in alarm..

S3, S103 positions 1,2,3,4 to OFF - ICS is disabled (Minimum Auto switching, Return to Last 
State Mode)

 The 1582-14 goes to the last state (CH1 or CH2) it was in when in Auto after Manually or 

Remotely switching and returning to Auto. Auto switching occurs only if current channel alarms and the 
other channel is clear.

S3, S103 normal position - 1,2,3,4 to ON

S4, S104 - CH1 CLOCK TIMEOUT

 - Selects the time in seconds (0.1 to 0.9) of data absence in channel 1 

before an alarm is indicated.

S5, S105 - CH2 CLOCK TIMEOUT

 - Selects the time in seconds (0.1 to 0.9) of data absence in channel 2 

before an alarm is indicated.

1582-14 Manual_A

 

 

  Page 8

    

    06/22/09

Содержание 1582-14

Страница 1: ...n are proprietary to Cross Technologies Inc but may be reproduced or duplicated without the prior permission of Cross Technologies Inc for purposes of operating the equipment When ordering parts from...

Страница 2: ...anship for a period of one year after shipment to customer Cross Technologies Inc s obligation under this warranty is limited to repairing or at Cross Technologies Inc s option replacing parts subasse...

Страница 3: ...nd CH2 are in alarm 3 Minimum Auto switching Initial Channel Select ICS Mode Switch stays on channel last selected by Manual or Remote selection after return to Auto if both channel alarms are clear o...

Страница 4: ...arm SWITCH RESET Resets switch to CH1 if it is good and switch is in the latch mode Also Resets REMOTE by returning operation to Auto Indicators LEDs CH1 ON LINE Turns green when Channel 1 is selected...

Страница 5: ...N 1 2 4 6 7 9 Not connected J8 Monitors and Cont trols Controls Connec ctor J8 Monitors and Controls Connector Function Pin Description ALARM 1 IN 13 Ground or Open selectable by JP2 JP102 gives CH1 a...

Страница 6: ...RM CH2 LED Turns red when Channel 2 clock times out or on external alarm input REMOTE LED Turns amber when REMOTE control is active MANUAL SELECT Switch 3 position switch as follows LEFT manually sele...

Страница 7: ...el 2 and stays there until the reset button is pushed on the front panel or by an external closure to ground on the remote RESET pin on J8 and then it switches to channel 1 If channel 1 alarms are cle...

Страница 8: ...tion DIP switch Selects the Initial Channel Select mode when JP1 2 3 JP101 102 103 in Dot and JP4 JP104 in Non dot S3 S103 positions 1 2 3 4 to ON ICS is enabled In the ICS mode the initial channel ca...

Страница 9: ...djust these switches to the desired length in 0 1 second increments position 1 0 1 seconds position 2 0 2 seconds etc see Figure 2 3 JP4 JP9 1 2 3 4 O F F ROCKER DOWN S3 ROCKER SWITCH DETAIL SHOWN WIT...

Страница 10: ...ual or Remote selection after return to Auto if both channel alarms are clear or both channels are in alarm Auto switching occurs only if current channel alarms and the other channel is clear Non dot...

Страница 11: ...he equipment is not compromised Additional space between unit may be required E Circuit Overloading Consideration should be given to the connection of the equipment to the supply circuit and the effec...

Страница 12: ...CHNOLOGIES INC 6170 Shiloh Road Alpharetta Georgia 30005 770 886 8005 FAX 770 886 7964 Toll Free 888 900 5588 WEB www crosstechnologies com E MAIL info crosstechnologies com 1582 14 Manual_A Page 12 0...

Отзывы: