Display shows “Calibration Failure”.
The span calibration failed. Try to recalibrate the sensor again. If re-calibrating the sensor fails,
replace the sensor.
LPT-P powered up (display appears normal) but the control panel displays “Fault”.
Modbus® output signal has not been connected properly. Check the connections and refer to the
Wiring Examples in Section 5.6 Wiring Connections.
LPT-P Device cannot be seen by the Controller and/or the BAS / DDC on the Modbus®
network.
• Check the Baud rate. All devices in the network must have the same Baud rate. Refer to
Section
6.7.2 Change Modbus® Baud Rate.
• Check the Modbus® ID. Each device must have a unique ID assigned to it. Refer to Section
6.7.1 Change Modbus® ID.
• Check that local area network wiring is correct, especially the A and B lines to make sure
they are not swapped between devices on the network.
• Check that local area network wiring is correct, especially the A and B lines to make sure
they are not swapped between devices on the network.
Frequent, unexpected alarm conditions.
Check to see if EMI and RF interference is causing the
equipment to react this way. Refer to Section
5.4.2 EMI and RF Interference Considerations
for more
information.