LPT-P- Operation Manual
calibration should be done in that same temperature range.
5.1 General Safety Warnings
The LPT-P is intended for indoor use, permanently mounted at a height that is appropriate for
the type of gas being monitored. See Section
5.4 Mounting the Transmitter
. The LPT-P should be
protected from extreme weather conditions.
The LPT-P requires no assembly and virtually no maintenance other than regular calibration of the
integral and/or remote sensors and ensuring that excess water or dust is not somehow entering
the enclosure and physically damaging the circuit board or internal components. There are no
serviceable elements other than the calibration instructions outlined in this manual. There are no
replaceable components except the sensors.
5.2 Protection Against Electrical Risks
Disconnect all power before servicing. There may be multiple power sources. Power supply may
have a building installed circuit breaker / switch that is suitably located and easy to access when
servicing is required and should be labelled as LPT-P supply (disconnecting power to the LPT-P).
Appropriate markings should be visible at the circuit breaker / switch that is supplying power to
the LPT-P.
This device may interfere with pacemakers. Modern pacemakers have built-in features to protect
them from most types of interference produced by other electrical devices you might encounter in
your daily routine. If you a have a pacemaker, follow your healthcare provider’s instructions about
being around this type of equipment.