LPT-P - Operation Manual
Rev. B | 2018.08
6.7.3 Modbus® Holding Registers
If you ha
ve specifi c requirements, have any questions or require clarifi cation about the Modbus®
holding registers, please contact CETCI for assistance.
6.8 Setting Channel Alarm Setpoints
The LPT-P is confi gurable as a one, two or three channel gas detector and each channel has three
gas alarm setpoints, LOW, MID and HIGH which can be ascending or descending. The number
entered as the setpoint is the exact number at which the gas concentration reading will be
determined as being LOW, MID or HIGH. The information will be read by the Controller or BAS and
the appropriate safety measures, such as triggering a relay(s), sounding an alarm, etc. will occur as
programmed into the Controller or BAS.
Almost all installations will use the factory default alarm setpoints. The default setpoints are:
SENSOR GAS TYPE
LOW ALARM
MID ALARM
HIGH ALARM
Carbon Monoxide (CO)
25 ppm
50 ppm
100 ppm
Nitrogen Dioxide (NO
2
)
0.7 ppm
1.0 ppm
1.5 ppm
Combustibles (catalytic)
10% LEL
15% LEL
20% LEL
NOTE:
If Channel 1 is not being set, follow the same steps using Channel 2 and/or Channel 3.
6.8.1 Setting the Low Alarm Setpoint
In the Sensor Confi guration Menu (passcode 3032), press either ARROW key to scroll through the
menu and select the channel for which you are setting the alarm setpoint.