LPT-P - Operation Manual
Rev. B | 2018.08
Calibration Kits and gases are available from the CETCI factory. Many gases, but not all are carried
in inventory. Check with any CETCI authorized distributor for availability of specifi c gas types.
Gas
cylinders cannot be shipped from Canada to other countries, including the USA.
For more
9 MAINTENANCE
The LPT-P transmitter requires virtually no maintenance other than regular calibration of the
sensor.
The transmitter should be monitored for possible damaging conditions.
• The sensor port should be kept free of dirt or soot build up.
• If in a damp location, source of water should be shielded from contacting the top of the
transmitter.
• If located in a working area, the front of the transmitter should be kept clear.
• If painting is to be conducted in the transmitter’s location the transmitter needs to be
protected from over spray and the sensor port should not receive paint fumes – these fumes
may damage or reduce the life of the sensor.
11 TROUBLE SHOOTING
LPT-P won’t power up. (blank display)
Is the power properly connected? Check the connections. Refer to Section
5.6 Wiring Connections
.
Check the display contrast. Refer to Section
6.5 Set LCD Display Contrast Level.
Display shows a channel status FAULT message.
The LPT-P is in fault mode. If re-calibrating the sensor fails, replace the sensor.