LPT-P- Operation Manual
NOTE: WARRANTY VOID IF SOLID-CORE WIRE IS USED AT THE WIRING TERMINAL STRIP.
When using solid core wiring for distribution (in the conduit), use stranded wire pigtails 18 AWG
within the enclosure to connect to the circuit board. The rigidity of solid-core wire can pull a
soldered terminal strip complet
ely off a circuit board and this will not be covered under warranty.
5.6.1 Power & Output Connections
If the LPT-P is being connected to either a QCC or FCS the supply voltage will either be supplied by
the QCC or FCS and any additional power requirements of the system will be supplied by RPS-24VDC
Remote Power Supply devices. If the LPT-P is being used on systems other than a QCC or FCS then
either 24 VDC power supplies or 24 VAC Class 2 Transformers need to be used. In all cases the
voltage supply to the LPT-P should never drop below 18 VDC or 20 VAC.
System power:
The main wiring terminal strip on the LPT-P circuit board can be unplugged for
easier wiring installation. Grasp the two sides of the terminal strip and pull sideways.
Device must be used with rated equipment. External power to LPT-P must be supplied by a Class 2
or better transformer.
Wiring Example: 4-Wire 24 VDC