LPT-P- Operation Manual
Press ENTER and use the ARROW key to scroll to the Enable screen. Use the ENTER key to choose ON
or OFF. Use the ARROW key to move on to the next menu item and ENTER to Exit.
6.10 Test Gas Reading Response / Send Test Reading to
Controller
NOTE:
Before conducting this test, notify the appropriate people so unnecessary distress or
response is not caused.
NOTE:
This functionality is available in fi rmware version 1.29 onwards.
This test allows you to send a forced gas reading to the controller without having to expose the
sensor to actual gas, so you can make sure the LPT-P is connected to the controller properly after
installation and is still initiating an appropriate response from the controller during routine
maintenance checks. The test only applies to the channel you have chosen.
In the Sensor Confi guration Menu (passcode 3032) press either ARROW key to scroll through the
menu and select the channel for which you want to test the gas reading response.